Troubleshooting Guide
Problem | Probable Cause | Remedy |
COMPRESSOR RUNS BUT | Condenser fan not running. | Check that the condenser fan is |
NO COOLING. TRIPPING |
| running. If the fan is binding or |
OVERLOAD. |
| turning slowly, an overload condition |
(Compressor shell is hot to |
| will occur. |
touch). |
|
|
| Inadequate air flow through | Air flow is top front in, exhaust out |
| the dispenser. | the rear. NEVER PLACE |
|
| ANYTHING ON TOP OF THE |
|
| DISPENSER. This will block the |
|
| airflow over heating the compressor |
|
| and causing it to trip the overload. |
| Blocked condenser fins. | Remove the rear bonnet and check |
|
| the condenser fins. If unit is run in a |
|
| dusty environment, condenser fins |
|
| can become clogged, stopping the air |
|
| flow. |
|
| Brush out and clean with vacuum. |
| Ambient air over 100°F 38°C. | If the dispenser is working in an |
|
| environment over 100° ambient or is |
|
| drawing in discharged air, during a |
|
| heavy period, the unit may trip the |
|
| overload. |
| Defective overload. | Overload works on shell temperature |
|
| and amperage draw and can be |
|
| defective. Replace as needed. |
| Defective compressor. | Refrigeration technician will verify if |
|
| the compressor is defective and needs |
|
| to be replaced. |
UNIT IS DISPENSING | Insufficient water level in the | See the |
CONCENTRATE ONLY | water bath. | Section of this manual. Be sure the |
REFRIGERATION SYSTEM |
| water bath is filled to fill line. |
HAS BEEN RUNNING FOR |
|
|
EXTENDED PERIOD | Agitator motor not operating. | Check the agitator motor located on |
WITHOUT SHUTTING OFF |
| the refrigeration deck. Be sure it is |
FROZEN WATER COIL. |
| plugged in and receiving power. |
|
| Check that the impeller is not |
|
| obstructed. Replace if needed. |
| Improperly located ice bank | Melt the ice bank and check the |
| control sensor. | location of the sensing bulb. Be sure |
|
| it is all the way down to the bottom |
|
| of the tube. |
16