2.C NO ICE ON EVAPORATOR

 

IS

 

IS

 

NO

HARVEST

YES

NO

 

TIMER

 

EVAPORATOR

 

 

RUNNING?

 

COLD?

 

YES

 

IS

NO

WATER LEVEL

 

NORMAL?

 

YES

 

 

CHECK WATER

 

PROBLEMS IN 2.A

CHECK

 

REFRIGERATION

 

SYSTEM.

 

YES

IS

HOT GAS SOLENOID

 

 

ENERGIZED?

 

 

NO

 

 

 

 

 

1.CHECK FOR REFRIGERANT UNDER-CHARGE.

2.CHECK HOT GAS SOLENOID FOR LEAKING SEAT.

3.GO TO 2.A.

 

YES

 

IS

NO

 

 

 

 

COND. CONTROL

 

 

 

 

 

ENERGIZED?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHECK TIMER

1.

CHECK FOR OPEN CONDUCT

SWITCH #1.

 

PROBE WIRING.

 

2.

CHECK CONDUCTIVITY

 

 

 

CONTROL.

IS

YES HARVEST TIMER HOME?

NO

1.CHECK ADJUSTMENT OF TIMER CAM #2. (HOT GAS)

2.CHECK TIMER SWITCH #2.

1.CHECK ADJUSTMENT OF TIMER CAM #1. (TIMER HOME)

2.CHECK TIMER SWITCH #1.

3.CHECK TIMER MOTOR.

23

91704

Page 26
Image 26
Cornelius SID650A/80-BC, SID650W/80-BC manual No ICE on Evaporator Harvest YES