GreenLight | Crestron Residential Lighting Design Guide |
CAEN Wiring
CAUTION: All power feeds must be protected by 15 or 20 amp circuit breakers (supplied by others).
NOTES: Use copper conductors only – rated 75°C
All wiring must be installed in accordance with all local and national electrical codes.
Two snap bushings are supplied. If required, insert into knockouts at the bottom of the enclosure to prevent damage to low voltage wiring.
Class 2 field wires must be kept separate. Refer to the illustration showing singlewide and doublewide wiring details. Areas for high voltage (Class 1) wiring are shown along the top and side(s) of the unit. The lower area is reserved for low voltage (Class 2) wiring.
Tighten all
CAUTION: Failure to properly tighten the screws may result in poor electrical connection and overheating of the terminals.
Wire Range & | CLT | Grounding Terminal | |||
Torque Data | Terminal |
| Blocks |
| |
| Blocks |
|
|
|
|
Wire Range | 22 - 10 | 14 - 10 |
| 8 | 6 - 4 |
|
|
|
|
|
|
Torque | 9 | 35 |
| 40 | 45 |
|
|
|
|
|
|
Doc. 5999F | 14 |