1. INSTALLATION GUIDE
1INSTALLATION PLACE
◆Indoor unit | ◆Outdoor unit |
• Flat and strong place in the room | • A place no reach of direct ray of sun (if necessary, shield the |
• No obstacles in front of air in/out grille | light) |
• Easy place to connect drain hose to outside of room | • No obstacles in front of air in/out grille |
• Easy place to connect copper tube with outdoor unit | • A place having a drain |
• Secure enough distance from neighboring objects as | • Easy place to connect copper tube with indoor unit |
shown below. | • Secure enough distance from neighboring objects as shown |
• Secure enough distance from neighboring objects as | below. |
shown below. |
|
CAUTION : Do not hang the outdoor unit on the wall of building, in case of falling, it may cause a serious trouble and damage.
2SPACE TO INSTALL
Secure enough space from the neighboring objects as shown below.
This is required to operate the unit efficiently.
100cm
(Indoor unit)
10cm
50cm
5cm
10cm | 50cm |
(Outdoor unit)
◆Specification and method of copper tube
•Connection method of copper tube is to make connection with flare nut at the end of the copper tube with a flare tool.
Flare specification
Unit: mm
B | Nominal diameter | A | B | ||
Lquid | 3/8” | 12~12.4 | 9.52 | ||
| |||||
| Gas | 5/8” | 18.6~19 | 15.88 | |
| Torque |
|
| Unit: mm | |
|
|
| Torque | ||
| Lquid | 3/8” | 300Kg • cm | ||
| Gas | 5/8” | 500Kg • cm |
2