![Chart 4.1 - Troubleshooting Guide](/images/new-backgrounds/43735/4373541x1.webp)
Dayton Installation, Operation, Maintenance and Parts Manual
Models 1RVT7 and 1RVT8
Chart 4.1 - Troubleshooting Guide
Symptom
Possible Cause
Corrective Action
Burning of | • Heater mounted at incorrect angle. | • Mounting angle 0˚- 30˚. |
|
plenum (flashback). | • Excessive drafts. | • Relocate or shield from draft. |
|
| • Gas leaking at orifice. | • Check with leak detector solution. |
|
| • Separation of ceramic grids. | • Replace burner. |
|
| • Ceramic grids cracked. | • Replace burner. |
|
Delayed ignition. | • Electrode out of specification. | • See ignition system insert. |
|
| • Low gas pressure. | • See Section 2.0, Gas Supply. |
|
| • Partially blocked orifice. | • Clean or replace. |
|
| • Improper orifice size. | • Consult Dealer. |
|
| • Incorrect gas. | • See unit nameplate. |
|
Low ceramic surface | • Dirty or plugged burner ceramics. | • See periodic maintenance instructions. |
|
temperature or excessive | • Partially blocked orifice. | • Remove and clean. |
|
rollout. | • Low inlet gas pressure. | • See Section 2.0, Gas Supply. |
|
| • High or low manifold gas pressure. | • Adjust main valve regulator as specified. |
|
| • Foreign matter in venturi tube. | • See periodic maintenance instructions. |
|
| • Excessive dark spots on burner. | • See periodic maintenance instructions. |
|
| • Gas supply piping too small. | • Increase inlet pressure or replace piping. |
|
| • Incorrect gas. | • See unit nameplate. |
|
Control system overheating. | • Heater not mounted correctly. | • Mounting angle 0˚- 30˚. Level left to right. |
|
| • Heater mounted too close to ceiling. | • Observe clearance to combustibles. |
|
Gas odor. | • Loose pipe connection. | • Check connections. Tighten as necessary. |
|
Heater cycles repeatedly. | • Heater located in drafty area. | • Relocate or shield from draft. |
|
| • Low gas pressure. | • See Section 2.0, Gas Supply. |
|
| • Thermostat located in drafty area. | • Relocate thermostat. |
|
| • Defective electrode or circuit board. | • Replace. |
|
No spark; no ignition. | • Lack of 120V incoming voltage. | • Check power supply. |
|
| • Open high voltage wire. | • Isolate an ohm for resistance, replace if 0. |
|
| • Fan not operating. | • Locate source of electrical problem or |
|
|
| replace faulty fan. |
|
| • Improper electrode gap. | • See Ignition System specifications. |
|
| • Loose or open wire connection. | • Check all wires, tighten or replace. |
|
| • Pressure switch not satisfied. | • Verify fan operation. Remove obstructions. |
|
| • Poor or no equipment ground. | • Check all connections, provide positive |
|
|
| earth ground. |
|
| • Unit in “safety lockout” mode. | • Interrupt power source, repeat trial for ignition. |
|
| • Defective “gaslighter” control. | • Replace. |
|
Heater lights, and “locks out” | • Poor or no equipment ground. | • Check all connections, provide positive |
|
after approximately 10 seconds. |
| earth ground. |
|
| • Polarity is reversed. | • 120V to black, neutral to white. |
|
| • Low gas pressure. | • See Section 2.0, Gas Supply. |
|
| • Electrode not sensing. | • Relocate or replace if defective. |
|
| • Heater mounted at incorrect angle. | • Mounting angle 0˚- 30˚. |
|
| • Defective “gaslighter” control. | • Replace. |
|
Spark is present. No main gas | • Gas valve in “OFF” position. | • Turn to “ON” position. |
|
operation. Unit “locks out”. | • Defective gas valve. | • Isolate and check for resistance, replace if 0. |
|
| • Defective “gaslighter” control. | • Replace. |
|
Heater will not shut off. | •Defective thermostat or wiring. | • Replace or repair. |
|
| • Gas valve stuck or open. | • Replace. |
|
| • High gas pressure. | • See Section 2.0, Gas Supply. |
|
|
|
|
|
®
21