INSTALLATION

INSTALLATION:

The Del Rey Heater provides radiant warmth *indoors (commercial applications only) or outdoors with a powerful 58,000 Btu/hr natural gas. All units are equipped with hot surface ignition and 100% shutoff valve for safety. Del Rey Heaters to be installed in Aircraft Hangers must be installed in accordance with American National Standards for Aircraft Hangers, ANSI/NFPA No. 409. Heaters to be installed in public garages must be installed in accordance with NFPA No. 88A standards for parking structures. Heaters must be installed so that minimum clearances marked on the heater will be maintained from vehicles parked below the heater.

The installation must conform with ANSI standard No. Z223.1 National Fuel Gas Code and any applicable local codes. In Canada, the installation must conform with local building codes or, in the absence of local codes, with National Standards of Canada CAN/CGA-B 149.1 & 2-M86. Each heater must be electrically grounded in accordance with the National Electrical Code, ANSI/NFPA 70 when an external electrical source is utilized. In Canada, the CSA Canadian Electrical Code, C22.1, Part 1 applies.

The gas inlet supply and normal operating manifold pressure for each heater are as follows. For gas supply line pressures in excess of 1/2 psig, contact your dealer or the factory.

GAS INLET PRESSURE

maximum: pressure Natural Gas: 1/2 psig

minimum: pressure Natural Gas: 6 W.C.

manifold: pressure Natural Gas: 5 W.C.

The heater has an internal 5”W.C. regulator.

Note: This unit is for use with natural gas only.

WARNING:

1.This product must be installed by a licensed plumber or gas fitter when installed within the Commonwealth of Massachusetts.

2.When installing Mounting Body Assembly, make sure left hand and right hand Body Assembly are level. If not, escaping heat could easily cause damage to the components inside the compartment.

9

Page 10
Image 10
DCS DRH48N installation instructions Installation, GAS Inlet Pressure