Defy Appliances Part Number 059 044 Silhouette Console Installation instructions

Models: Part Number 059 044

1 8
Download 8 pages 34.29 Kb
Page 3
Image 3
Silhouette Console Installation instructions

Silhouette Console Installation instructions

900

720

550 390

220

310

CONSOLE UNIT

MOUNTING HOLES

MOUNTING HOLES

735

400

335

WALL SLEEVE

WALL APERTURE

100

405

745

100mm.

ABOVE FINISHED FLOOR LEVEL (INDOOR)

PRIOR TO INSTALLATION

Remove the filter assembly.

Loosen the two screws at the bottom corners of the access cover and remove it.

Loosen the two screws at either end of the fan deck.

Disconnect the multi-plug and slide the fan deck out.

Protect the deck against dust generated during the installation process.

Secure the unit to the wall using at least four of the fixing holes provided. ( See sketch above )

Ensure that the unit is properly and accurately fitted to the wall sleeve assembly.

Should the factory fitted condenser coil foam seals not butt up to the louver assembly, insulated divider plates must be fitted to prevent hot air re-circulation back into the condenser section.

It is also advisable to remove the side deflectors from the condenser coil and fit them directly behind the louvre.

ELECTRICAL CONNECTION

Ensure that the supply voltage is 230V 50 Hz

This unit must be earthed and installed in accordance with local municipal safety standards.

If necessary, ensure that a qualified electrician replaces the mains cable.