Table 15. Typical Alarms and Conditions (continued)

Alarm or Condition

Possible Cause

Action

 

 

 

Output Overload

The load level is at or has

The UPS can support the load indefinitely at

(Alarm 25)

exceeded the configurable

this load level.

threshold limit for a Level 1

 

Continuous Alarm

The alarm clears when the load drops below

Overload condition.

5% of the set point.

 

 

 

 

 

 

 

 

Output Overload Level 2

The load level is >101% and

Remove some of the equipment from the

(Alarm 159)

<110% of the UPS rating.

UPS. The UPS continues to operate, but

 

transfers to Fault mode in two minutes.

Continuous Alarm

 

 

The alarm clears when the load drops below

 

 

 

 

 

 

5% of the set point.

 

 

 

Output Overload Level 3

The load is >110% of the UPS

Remove some of the equipment from the

(Alarm 162)

rating.

UPS. The UPS continues to operate, but

 

transfers to Fault mode in 300 ms to one

Continuous Alarm

 

 

second.

 

 

 

 

 

 

The alarm clears when the load drops below

 

 

 

5% of the set point.

 

 

 

Battery DC Over Voltage

Battery voltage levels have

The UPS turns off the charger until the next

(Alarm 68)

exceeded the maximum

power recycle. Contact your service

allowable limits.

representative.

Continuous Alarm

 

 

 

 

 

Charger Failure

A battery charger fault has been

The UPS turns off the charger until the next

(Alarm 34)

detected.

power recycle. Contact your service

 

representative.

Continuous Alarm

 

 

 

 

 

 

Inverter AC Over Voltage

The UPS has detected

The UPS transfers to Bypass mode if

(Alarm 0)

abnormally high inverter

supporting the load.

voltage levels.

 

Continuous Alarm

 

 

 

 

 

 

Inverter AC Under Voltage

The UPS has detected

The UPS transfers to Bypass mode if

(Alarm 1)

abnormally low inverter voltage

supporting the load.

levels.

 

Continuous Alarm

 

 

 

 

 

 

Rectifier Input Over Current

The UPS has detected that

The UPS transfers to Bypass mode if

(Alarm 26)

rectifier input current limits

supporting the load.

have been exceeded.

 

Continuous Alarm

 

 

 

 

 

 

Inverter Output Over

The UPS has detected that the

The UPS transfers to Bypass mode if

Current

inverter output current limits

supporting the load.

(Alarm 27)

have been exceeded.

 

 

 

Continuous Alarm

 

 

 

 

 

 

70

Troubleshooting

 

 

Page 70
Image 70
Dell K805N, J739N, K804N, 3750W, J730N, H952N, 4200W manual Troubleshooting

H952N, K804N, J739N, K805N, J730N specifications

The Dell J730N, K805N, J739N, 4200W, and 3750W are all high-performance server power supplies designed to provide reliable power solutions for various Dell server models. These power supplies are engineered to ensure maximum uptime, energy efficiency, and seamless operation in data center environments.

Starting with the Dell J730N, this power supply unit is known for its robust design and 730W output capacity. It features hot-swappable functionality, allowing for easy replacement without powering down the server. This is crucial for mission-critical applications where downtime can lead to significant operational challenges. The J730N is compatible with various Dell servers, making it a versatile choice for data centers looking to enhance their power management.

The K805N power supply is another excellent option with a power output of 800W. It incorporates advanced features such as Automatic Voltage Regulation (AVR), which ensures that the output voltage remains stable even during fluctuations in the input voltage. This technology is vital for protecting sensitive server components from potential damage caused by power inconsistencies. Additionally, the K805N is designed with a modular approach, allowing for easy integration and scalability.

The Dell J739N exemplifies Dell’s commitment to energy efficiency with its 750W rating. It meets stringent efficiency standards, making it an environmentally friendly option that helps reduce power consumption and operational costs. The J739N is often used in combination with other Dell equipment to create a cohesive and efficient power management strategy. Its reliability is bolstered by a combination of intelligent internal monitoring systems that detect and address power anomalies.

The 4200W and 3750W power supplies represent higher capacity options for larger, more demanding server environments. These units are equipped with multiple redundant power circuits, ensuring that if one circuit fails, others will continue to supply power without interruption. The advanced cooling technologies utilized in these models also enhance performance and reliability by preventing overheating.

Overall, these Dell power supplies reflect the highest standards in design and technology. They are integral to maintaining the health and efficiency of server operations, contributing significantly to the resilience and effectiveness of data-centered environments. With a focus on compatibility, energy efficiency, and reliability, the J730N, K805N, J739N, 4200W, and 3750W power supplies remain essential components in modern IT infrastructures.