Delta Electronics DVP-01HC Trial Run & Troubleshooting, Relative Instructions, From, DC 5~24VDC

Models: DVP-01HC

1 2
Download 2 pages 12.89 Kb
Page 2
Image 2
DC 5~24VDC

 

 

#4

 

H4162

R/W

 

instruction

Instruction, factory setting: K0

 

 

 

 

 

 

 

 

1.

When b0 is set to 1 and terminal “DIS” is off, count

 

 

CR#4

 

‘0’(Off)

 

‘1’ (On)

 

 

 

 

 

 

 

 

 

 

 

 

 

is enabled.

 

 

b0

Count is disabled

Count is enabled

 

 

 

2.

When b1 is set to 1, YH0 (hardware comparison

 

 

b1

YH0 output is

 

YH0 output is enabled

 

 

 

 

output) output is enabled.

 

 

 

disabled

 

 

 

 

 

 

 

 

 

 

3.

When b2 is set to 1, YH1 (hardware comparison

 

 

 

 

YH1 output is

 

 

 

 

 

b2

 

YH1output is enabled

 

output) output is enabled.

 

 

 

disabled

 

 

 

 

 

 

 

 

 

 

4.

When b3 is set to 1, YH0 and YH1 affect each

 

 

 

 

 

 

 

 

 

YH0 and YH1 affect

 

 

 

 

YH0 and YH1

 

 

other (they cannot be ON/OFF simultaneously). In

 

 

 

 

 

each other (they

 

 

 

 

b3

 

activate

 

 

 

other words, when YH0=ON, YH1 must be OFF

 

 

 

 

cannot be ON/OFF

 

 

 

 

 

independently

 

 

and when YH0=OFF, YH1 must be ON. When

 

 

 

 

 

simultaneously)

 

 

 

 

 

 

 

 

 

 

 

 

 

b3=0, YH0 and YH1 activate independently.

 

 

b4

Preset disabled

Preset is enabled

 

 

 

5.

When b4=0, terminal “PRE” is disabled.

 

 

b5~b7

Reserved

 

6.

When b8=1, all error flags (CR#29) will be cleared.

 

 

b8

Not used

 

Clear error flag

7.

When b9=1, YH0 output will be cleared to be OFF.

 

 

b9

Not used

 

Clear YH0 output

8.

When b10=1, YH1 output will be cleared to be

 

 

b10

Not used

 

Clear YH1 output

 

OFF.

 

 

b11

Not used

 

YH0 output setting

9.

When b11=1, YH0 output will be ON.

 

 

b12

Not used

 

YH1 output setting

10.When b12=1, YH1 output will be ON.

When current value of counter = comparison value, output

 

current value

current value

YH0/YH1 will be ON and hold. User can clear output point by

 

of counter

of counter

using b9 and b10 of CR#4.

 

 

 

Comparison

 

Comparison

 

 

If count value

= comparison value by

using PRESET or

 

 

 

 

instruction TO, corresponding output YH0 or YH1 will be OFF. In

 

 

value

 

 

value

 

 

 

 

 

 

 

 

 

 

 

 

other case that count value = comparison value does not use

 

current value

current value

PRESET or instruction TO, corresponding output YH0 or YH1 will

 

of counterCR#4

of counter CR#4

be ON.

 

 

 

 

 

b9, b10 SET

 

 

b9, b10 SET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#16~ #19

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current value of counter (#20: Lower word / #21: Upper word),

 

 

factory setting is K0.

 

 

 

 

 

 

Current value of

Setting notes:

 

 

 

 

 

 

 

 

 

 

 

 

it must write with 32-bit.

 

 

 

 

 

#21 #20 H4172

R/W counter

In 16-bit mode,

value that is written must be less than ring

 

 

length (CR#2).

 

 

 

 

 

 

 

 

 

 

 

 

 

In 16-bit mode, CR#21 will be cleared to 0 when writing into

 

 

current value of counter.

 

 

 

 

 

YH0+

YH1+

Load

YH0+

YH1+

load

 

 

DC 5~24VDC

 

 

DC 5~24VDC

YH0-

YH1-

 

YH0-

YH1-

 

5.Before power up, check if A phase or B phase connects to correct voltage level. (there are three voltage level: +24, +12V and +5V) If +24V signal connects to +5V input terminal, it may damage internal circuit.

6.After power up MPU, it will start to detect extension module. If no external +24VDC power is applied to HC at this time or power is applied after EH MPU completing detecting extension module, the connection will fail. Therefore, power wiring and power supply timing should be as following.

b13~b15

Reserved

Setting notes:

1.After setting CR#4, b8~b12 will be cleared to 0.

2.It needs to set to disable count(b0=0) before setting count mode (CR#5).

 

 

#5

H4163

 

R/W

Count mode setting

Count mode K0~K11, factory setting is K0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Count mode

 

 

CR#5 settings

 

 

 

 

 

 

 

 

 

 

32 bits

 

16 bits

 

2-phase 2 inputs

 

 

Normal frequency

 

K0

 

K1

 

 

 

 

 

 

 

Double frequency

 

K2

 

K3

 

 

 

 

 

 

 

Four times frequency

 

K4

 

K5

 

 

 

 

1

-phase 2 inputs

 

K6

 

K7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Count mode

 

 

CR#5 settings

 

 

 

 

 

 

 

 

 

 

32 bits

 

16 bits

 

1-phase 1 input

 

Count Up/Down is controlled

 

K8

 

K9

 

 

by Hardware (Note 1)

 

 

 

 

 

 

 

 

 

 

 

 

#23 #22

H4174

R/W

Max. count value

Max. count value (#22: Lower word / #23: Upper word), factory

setting is K0.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#25 #24

H4176

R/W

Min. count value

Min. count value (#24: Lower word / #25: Upper word), factory

setting is K0.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#26

H4178

R

Comparison result

Comparison result

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CR#26

 

 

‘0’(Off)

 

‘1’(On)

 

 

 

 

CR#26

 

‘0’(Off)

 

‘1’(On)

 

 

 

 

b2

Setting value

Setting value >

 

 

 

b6

Setting value

 

Setting value > current

 

 

 

 

 

 

 

current value

current value

 

 

 

current value

 

value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YH0

 

b1

Setting value

Setting value =

 

YH1

 

b5

Setting value

 

Setting value = current

 

 

 

 

 

current value

current value

 

 

current value

 

value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b0

Setting value

Setting value <

 

 

 

b4

Setting value

 

Setting value < current

 

 

 

 

 

 

 

current value

current value

 

 

 

current value

 

value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#27

H4179

R

 

Action status

 

The indication of count up/down and terminal status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CR#27 ‘0’(Off)

 

‘1’(On)

 

 

 

 

 

CR#27

 

‘0’(Off)

‘1’(On)

 

 

b0

 

-

 

 

 

 

Count up

 

 

 

 

 

b4

 

PRE input is Off

PRE input is On

 

 

 

b1

 

-

 

 

 

 

Count down

 

 

 

 

 

b5

 

DIS input is Off

DIS input is On

 

 

 

b2

 

A input is off

 

A input is on

 

 

 

 

 

b6

 

YH0 output is Off

YH0 output is On

 

Power wiring

85~264VAC

 

 

 

Power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC/DC

 

 

 

+24V_EXT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+24V input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

N

 

G

 

 

 

 

 

 

 

 

 

+24V

0V

 

 

 

 

 

 

 

 

 

 

EH MPU

 

 

 

 

01HC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+24V

24G

 

 

 

 

 

 

 

 

 

+24V_INT

Timing analysis

When power supply for HC is +24V_INT:

t5t3, power is ON and the connection of HC extension unit is normal.

When power supply for HC is +24V_EXT:

Because start time (t2) of external power supply for HC extension module is unknown, user must make sure that t2+t4 t1+t5, otherwise HC extension module cannot be detected by MPU.

Power supply timing

AC power input 2 3 3 3 2 1

+24V_INT

 

 

t1

 

 

 

 

 

 

 

 

 

 

+24V_EXT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t2

complete initialling HC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(supply from +24_INT)

 

 

 

 

 

 

 

 

t3

 

 

 

 

 

 

 

 

complete initialling HC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(supply from +24_EXT)

 

 

 

 

 

 

 

 

 

 

 

t4

 

 

 

 

 

 

 

 

 

 

 

MPU starts to detect

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

extension unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t5

t1:1~2 seconds

t2:1~3 seconds

t3:0.5~1 seconds

t4:0.5~1 seconds

t5:2 seconds

Count Up/Down is controlled

K10

K11

by software (Note 2)

 

 

Note1: count up/down control is controlled by external input control.

Note2: count up/down control is controlled by internal control register(CR#1).

16-bit mode

 

When it is 16-bit mode, the count values are all positive value and its

count length

range is 0~65,536. When overflow event is occurred, count value will

CR#3, #2

be changed from upper limit to 0 or from 0 to upper limit. The upper

0

limit is set by CR#3 and CR #2.

 

32-bit mode

upper limit

+2,147,483,647

When it is 32-bit mode, the count range is -2,147,483,648 -

 

2,147,483,647. When overflow event is occurred, count value will

 

be changed from upper limit to lower limit or from lower limit to

 

upper limit. And upper limit is +2,147,483,647 and lower limit is

 

-2,147,483,648.

-2,147,483,648

 

lower limit

Setting notes:

1.It only can be written when count is disabled (bit 0 of CR#4 is 0).

2.After writing, it will initial controlled registers as follows: CR#1: 0. CR#2, 3: 65,536. CR#10: 0. CR#12, 13:

32,767. CR#14, 15: 32,767. CR#20, 21: 0. CR#22, 23: 0. CR#24, 25: 0.

 

1-phase 1 input (K8~K11)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-phase 2 inputs (K6~K7)

 

External input count up/down control

 

Internal controlled register count

1-phase 2 inputs counter (K6, K7)

 

(K8~K9)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

up/down control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CR#1

 

 

 

 

 

 

 

 

 

 

 

K1

A input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pulse of count up

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B input

 

 

 

Off (count up)

On (count down)

 

A input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pulse of count down

 

 

 

count up

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

count up

 

 

 

count down

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

count down

 

 

 

 

 

 

count value 1

2 3 3 3 2 1

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

count

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

count

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-phase 2 inputs (K0~K5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal frequency (K0, K1)

 

 

 

 

 

 

 

 

 

 

Double frequency (K2, K3)

Four times frequency (K4, K5)

 

A input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

count value

0 1 2 3 4

 

 

3 2 1 0

 

 

count value

01 2 3 4 5 67

 

 

7 6 5 4 3 2 1

 

 

count value 0

1 2

 

 

 

2

1

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#6 ~ #9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory setting for counter (#10: Lower word / #11: Upper word),

 

#11

#10

 

H4168

R/W

 

 

Factory setting

 

factory setting: K0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting notes: in 16-bit mode, CR#11 will be cleared to 0 when

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

writing factory setting.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YH0 comparison

 

YH0 output comparison value (#12: Lower word / #13: Upper

 

#13

#12

 

H416A

R/W

 

 

 

word), factory setting: K32,767.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

value

 

 

 

 

Setting notes: in 16-bit mode, CR#13 will be cleared to 0 when

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

writing YH0 comparison value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YH1 output comparison value (#14: Lower word / #15: Upper

 

#15

#14

 

H416C

R/W

 

 

YH1 comparison

 

word), (factory setting: K32,767).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

value

 

 

 

 

Setting notes: in 16-bit mode, CR#15 will be cleared to 0 when

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

writing YH1 comparison value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b3

 

B input is off

 

B input is on

 

 

 

b7

YH1 output is Off

YH1 output is On

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#29

 

H417B

 

R/W

 

Error status

 

Data register that is used to save all error status. Refer to

 

 

 

 

 

 

table below.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CR#29

 

 

 

 

 

 

 

 

 

 

Error Status

 

 

 

 

 

 

b0~ b3

 

 

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

b4

 

 

CR number that is designated by instruction FROM/TO exceeds the usage range

 

 

 

 

 

b5

 

 

Overflow indication, When count-up value exceeds upper limit(upper limit is CR#2 and #3

 

 

 

 

 

 

 

in 16-bit mode and it is K2,147,483,647 in 32-bit mode)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b6

 

 

Overflow indication, When count-down value is less than lower limit(lower limit is 0 in

 

 

 

 

 

 

 

16-bit mode and it is K-2,147,483,648 in 32-bit mode)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b7~ b15

 

 

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#30

H417C

R

 

System version

 

Hexadecimal, display current software version, such as version

 

 

 

 

 

1.0A will be displayed as H’010A.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#31

 

H417D

R/W

 

Communication

 

RS-485 communication address, range set: 01~255, factory

 

 

 

 

 

 

 

 

 

 

 

address

 

default value: K1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Baud rate setting: 4800,9600,19200bps,38400 bps,57600 bps,

 

 

 

 

 

 

 

 

 

 

 

 

 

115200 bps. ASCII mode data format is always 7Bit, even bit,

 

 

 

 

 

 

 

 

 

 

 

 

 

and 1 stop bit (7 E 1). RTU mode data format is always 8Bit,

 

 

 

#32

 

H417E

R/W

 

Baud Rate

 

even bit , and 1 stop bit ( 8 E 1)

 

 

 

 

 

 

 

Setting

 

b0: 4800 bps(bit/sec.), b1: 9600 bps(bit/sec.) (default value)

 

 

 

 

 

 

 

 

 

 

 

 

 

b2: 19200 bps(bit/sec.), b3: 38400 bps(bit/sec.)

 

 

 

 

 

 

 

 

 

 

 

 

 

b 4: 57600 bps(bit/sec.), b 5: 115200 bps(bit/sec.)

 

 

 

 

 

 

 

 

 

 

 

 

 

b6~b14: reserved, b15: ASCII / RTU mode switch

CR#0~CR#34: The corresponding addresses are H 415E-H 4180 for user to read/write by using RS-485.

1.Baud rate could be 4800, 9600, 19200, 38400 and 57600bps.

2.Communication protocol can be Modbus ASCII mode and RTU mode. For ASCII mode, data format is 7Bits, even, 1 stop bit (7 E 1). For RTU mode, data format is 8Bits, even, 1 stop bit (8 E 1).

3.Function code: 03H: read register data. 06H: write one WORD data into register. 10H: write multiple WORDs into register.

5

 

TRIAL RUN & TROUBLESHOOTING

MPU connects to HC extension module

1.Make sure that the power of MPU and extension unit is OFF before wiring.

2.Open extension port of EH MPU and connect to HC extension unit with cable. There is no connection order for EH MPU to connect extension unit, mix connection is allowed.

3.The power supply of HC extension unit must be external +24VDC power supply.

4.Before power up, check if the load circuit of output points YH0 and YH1 is correct, especially the circuit between YH0+, YH0- and YH1+, YH1-. There is a Zener Diode that is connected between YH0+, YH0- and YH1+, YH1- in HC. If the positive/negative pole is wrong, it may cause unexpected result.

7.The maximum special extension modules number for EH MPU connects is 8 special extension modules. After power is ON, EH will save module codes of connected special modules in D1320~D1327 in order. The module code of 01HC is H’0120. It indicates communication is OK when H’0120 is displayed in the corresponding special D register by using HPP02 or other monitor software.

Troubleshooting

Judge the errors by the indicators on the front panel. When errors occurred on DVP PLC, please check:

“POWER” LED

The “POWER” LED at the front of HC extension module will be lit (in green) if the power is on. If the indicator is not on when power up, please remove the wiring on terminals +24V. Once the indicator lights after this, it means that the 24V DC power supply of the PLC is overloaded. Please do not use the DC power supply from the +24V terminals, but use a DC24V power supply instead.

L.V. LED

The “L.V.” LED at the front of HC extension module will be lit if input voltage is not enough. The extension module won’t active at this time.

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RELATIVE INSTRUCTIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

API

 

 

 

 

 

 

FROM

 

 

 

 

 

 

 

 

 

 

 

 

 

Read Special Module CR Data

 

78

 

 

 

 

D

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: number of special module (m1=0~7).

: CR number of special module that will be

 

Instruction

 

 

 

 

 

 

 

 

 

 

 

 

Explanation

 

 

read.

: address for saving reading data.

: data number for reading once.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Writing special module #0 of CR#24 into D0 and special module #0 of CR#25 into D1. only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Program

 

 

 

 

 

write two data once (n=2).

 

 

 

 

 

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

X10

 

FROM

K0

K24

 

D0

K2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

API

 

 

 

 

 

 

 

 

TO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Special Module CR Data Write In

 

79

 

 

 

 

D

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: number of special module (m1=0~7).

: CR number of special module that will be

 

Instruction

 

 

 

 

 

 

 

 

 

 

 

 

 

Explanation

 

 

wrote in.

 

 

: data to write in CR.

: data number to write in once.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Using 32-bit instruction DTO to write D11 and D10 into special module#0 of CR#3 and CR#2.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Program

 

 

 

 

 

 

 

 

only write a data once (n=1).

 

 

 

 

 

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X11

 

 

DTO

 

K0

K2

D10

K1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 2
Image 2
Delta Electronics DVP-01HC Trial Run & Troubleshooting, Relative Instructions, From, DC 5~24VDC, 2 3 3 3 2