DVP02DA-S
1. | Status indicator (Power, RUN and ERROR) | 8. Expansion port | |
2. | Model name | 9. Expansion unit clip | |
3. | DIN rail clip | 10. | DIN rail (35mm) |
4. | I/O terminals | 11. | |
5. | I/O point indicator | 12. | Mounting rail of the expansion unit |
6. | Mounting hole of the expansion unit | 13. | DC Power input |
7. | Nameplate | 14. | Expansion port |
| 4 |
|
|
|
|
|
| CR (Control Register) |
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| Explanation |
|
|
|
|
|
|
| ||||||
| CR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| Parameters | Latched | Register Name |
|
| b15 | b14 | b13 | b12 | b11 | b10 | b9 | b8 | b7 | b6 | b5 | b4 | b3 | b2 | b1 | b0 |
| ||
| No |
|
|
| ||||||||||||||||||||
|
| Address |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| #0 | H 4032 | ○ R | Model type |
|
| System used, data length is 8 bits (b7~b0). |
|
|
| ||||||||||||||
| #1 | H 4033 | ○ R/W | Output mode setting |
|
|
|
|
|
| Reserved |
| CH2 |
| CH1 |
| ||||||||
|
|
|
|
|
|
|
| Output mode setting: factory setting is H0000. |
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
| Mode 0: output voltage mode (0V~10V). |
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
| Mode 1: output voltage mode (2V~10V). |
|
|
|
|
|
|
|
|
| Analog Output Module |
| |
|
|
| Instruction Sheet |
|
1 |
|
| WARNING |
|
|
|
|
|
|
|
|
|
|
|
Please carefully read this instruction thoroughly prior to use the
This is an
2.3External wiring
| Voltage output |
| |
* 2 | 0V ~ 10V |
| CH1 |
|
| ||
|
|
| V+ |
|
|
| I+ |
AC drive, recorder, | Isolation wire *1 | COM | |
scale valve... |
|
| FG |
| Current output | CH2 | |
| 0mA~20mA |
| V+ |
|
|
| I+ |
|
|
| COM |
AC drive, recorder, | Isolation wire *1 | FG | |
scale valve... |
|
|
|
terminal of |
|
|
|
power module |
|
|
|
| * 3 | DC24V | 24+ |
| System | 24- | |
|
| ||
| Grounding |
|
|
Class 3 Grounding |
|
| |
(100Ω or less) |
|
|
CH1
CH2
DC/DC +15V
AG
converter
Note 1: Please isolate analog output and other power wiring.
Note 2: If noise interferes from loaded input wiring terminal is significant, please connect a capacitor with 0.1~0.47µF 25V for noise filtering.
Note 3: Please connect power module
terminal and analog output module terminal to system earth point and make system earth point be grounded or connects to machine cover.
Warning: DO NOT wire to the No function terminal
|
|
|
|
| Mode 2: output current mode (4mA~20mA). |
|
|
|
|
| Mode 3: output current mode (0mA~20mA). |
|
|
|
|
| Mode 4: none use. |
#2 ~ #9 |
|
|
| Reserved | |
#10 | H 403C | ○ | R/W | CH1 output value | The output setting range of channel CH1~CH2 is K0~K4000. Factory setting is K0 |
#11 | H 403D | ○ | R/W | CH2 output value | and unit is LSB. |
#12~#21 |
|
|
| Reserved | |
#22 | H 4048 | ○ | R/W | To adjust OFFSET | It is used to set the OFFSET value of CH1~CH2. The setting range is |
|
|
|
| value of CH1 | |
#23 | H 4049 | ○ | R/W | To adjust OFFSET |
|
|
|
|
| value of CH2 |
|
#24 ~ #27 |
|
|
| Reserved | |
#28 | H 404E | ○ R/W | To adjust GAIN | It is used to set the GAIN value of CH~CH2. The setting range is | |
|
|
|
| value of CH1 | The factory setting is K2000 and unit is LSB. |
#29 | H 404F | ○ R/W | To adjust GAIN |
| |
|
|
|
| value of CH2 |
|
#30 | H 4050 | ╳ R | Error status | It is the data register to save all error status. Please refer to fault code chart for detail. | |
#31 | H 4051 | ○ R/W | Communication | It is used to set | |
|
|
|
| address setting | and the factory setting is K1. |
#32 | H 4052 | ○ R/W | Communication | It is used to set communication baud rate (4800, 9600, 19200, 38400, 57600, | |
|
|
|
| Baud Rate setting | 115200bps). Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1), |
metallic particles. Also, it is equipped with protective methods such as some special tool or key to open the enclosure, so as to avoid the hazard to users or any damage to the
Do not connect the AC power to any of the input/output terminals, or it may the
Do not touch the internal circuit for at least 1 minute after the power is Off.
| Make sure that |
2 | INTRODUCTION |
2.1Model Explanation and Peripherals
Thank you for choosing DELTA DVP PLC Series. The analog output module of
The software version of
Users can select output either voltage or current via wiring. Voltage output range is 0V ~ +10V DC (resolution is 2.5 mV). Current output range is 0mA ~ 20mA (resolution is 5 µA).
Nameplate Explanation
| P L C m o d e l |
|
|
Input power Supply Spec. |
| 20.4VDC ~ 28.8VDC | |
Analog Input /Output Module Spec. |
| 0V ~ + 10V or 0mA ~ +20mA | |
| 2.5 mV or 5 A | ||
|
|
| |
Barcode, series and version | VX.XX | ||
|
| ||
|
|
| MADE IN XXXXXX |
Model Explanation |
|
|
|
Model | Serial Number |
|
|
Product Series |
|
| Production series |
Input + Output points | S: for SS series MPU |
| Production week |
|
| Production year (2004) | |
| P: for EP series MPU |
| |
|
| Production place (Taoyuan) | |
| H: for EH series MPU |
| |
Model type |
| Serial number of version | |
|
| ||
AD: Analog input module | XA: Analog input/output mixed module |
| Production Model |
|
| ||
DA: Analog output module | RT: Resistor Thermocouple |
|
|
PT: Platinum temperature sensors | HC: Input module of |
|
|
TC: Thermocouple sensors (Type J/K) | PU: single axis positioning unit |
|
|
2.4Terminal of analog module layout
V+ | V+ | V+ | L+ | L+ | V+ | L1+ |
I+ | I+ | I+ | L- | L- | I+ | L1- |
COM | COM | COM | I- | SLD | COM | L2+ |
FG | FG | FG | FG | L+ | V+ | L2- |
V+ | V+ | V+ | L+ | I+ | L3+ | |
I+ | I+ | I+ | L- | L- | COM | L3- |
COM | COM | COM | I- | SLD | V+ | L4+ |
FG | FG | FG | FG |
| I+ | L4- |
|
|
|
|
| COM | FG |
V+ |
| V+ | L+ | L+ | V+ | L51 |
I+ |
| I+ | ||||
COM |
| I+ | L- | L- | COM | L5- |
FG |
| COM | I- | SLD | V+ | L6+ |
V+ |
| FG | FG | L+ | I+ | L6- |
| V+ | L+ | L7+ | |||
I+ |
| L- | L- | COM | L7- | |
COM |
| I+ | V+ | |||
| COM | I- | SLD | L8+ | ||
FG |
| FG | FG |
| I+ | L8- |
|
|
|
| COM | FG | |
|
|
|
|
|
|
| 3 |
|
|
| STANDARD SPECIFICATIONS |
| |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| 3.1 Specifications |
|
|
|
| ||
| Digital/Analog (2D/A) Module |
| Voltage Output | Current Output |
| ||
| Power Supply Voltage |
| 24 VDC (20.4VDC~28.8VDC) |
| |||
| Analog Input Channel |
| 2 channels / each module |
|
| ||
| Analog Output Range |
| 0~10V | 0~20mA |
| ||
| Digital Data Range | 0~4000 | 0~4000 |
| |||
| Resolution |
| 12 bits (1LSB=2.5 mV) | 12 bits (1LSB=5 µA) |
| ||
| Output Impedance |
| 0.5Ω or lower |
|
| ||
| Overall Accuracy |
| ±0.5% of full scale of 25℃(77℉) |
|
| ||
|
| ±1% of full scale during 0~55℃ (32~131℉) |
| ||||
|
|
|
|
|
| ||
| Response Time |
| 3 ms × channels |
|
| ||
| Max. Output Current |
| 20mA (1KΩ~2MΩ) | - |
| ||
| Tolerance Carried Impedance |
| - | 0〜500Ω |
| ||
| Digital Data Format |
| 2’s complementary of |
| |||
| Isolation Method |
| Isolation between digital area and analog area. But no isolation |
| |||
|
|
|
|
| among channels. |
|
|
| Protection |
| Voltage output has short circuit protection but a long period of short |
| |||
|
| circuit may cause internal wire damage and current output break. |
| ||||
|
|
|
|
|
| ||
|
|
|
|
| MODBUS ASCII/RTU Mode. Communication baud rate of 4800 / |
| |
| Communication Mode |
| 9600 / 19200 / 38400 / 57600 / 115200. For ASCII mode, format is |
| |||
|
| 7Bits, even, 1 stop bit (7 E 1), while RTU mode format is 8Bits, even, |
|
|
|
|
| while RTU mode is 8Bit, even bit, 1 stop bit (8 E 1). |
|
| ||||||||||||||
|
|
|
| b0: 4800 bps (bit/sec). |
| b1: 9600 bps (bit/sec). (factory setting) | ||||||||||||||
|
|
|
| b2: 19200 bps (bit/sec). |
| b3: 38400 bps (bit/sec). |
|
| ||||||||||||
|
|
|
| b4: 57600 bps (bit/sec). |
| b5: 115200 bps (bit/sec). |
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
| b14: exchange low and high byte of CRC check code (only for RTU mode) |
|
| ||||||||||||||
|
|
|
| b15: ASCII / RTU mode selection |
|
| ||||||||||||||
#33 | H 4053 | ○ R/W | Reset to factory | b15 | b14 | b13 | b12 | b11 | b10 |
| b9 | b8 | b7 | b6 | b5 | b4 | b3 | b2 | b1 | b0 |
|
|
| setting and set |
|
|
|
| Reserved |
|
|
|
|
| CH2 |
| CH1 | ||||
|
|
| characteristics | Output latched setting, factory setting H0000. |
|
|
|
| ||||||||||||
|
|
| adjustable priority | Give CH1 setting for example: |
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
| 1. When b0=0, user can set OFFSET and GAIN value of CH1 (CR#22, CR#28). | ||||||||||||||||
|
|
|
|
| When b1=1, inhibit user to adjust OFFSET and GAIN value of CH1 (CR#22, | |||||||||||||||
|
|
|
|
| CR#28). |
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
| 2. b1 means if characteristic register is latched. b1=0 (factory setting, latched), b1=1 | ||||||||||||||||
|
|
|
|
| (not latched). |
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
| 3. When b2 is set to 1, all settings will be reset to factory setting. |
|
| ||||||||||||||
#34 | H 4054 | ○ R | Software version. | In hexadecimal to display software version. For example: H 010A means 1.0A. | ||||||||||||||||
#35~#48 |
| System used |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| ○ means latched. , ╳ means not latched. |
|
|
|
|
|
|
|
|
|
| |||||||||
| R means can read data by using FROM command via |
|
|
|
|
|
|
|
|
|
| |||||||||
| W means can write data by using TO command via |
|
|
|
|
|
|
|
|
|
| |||||||||
| LSB (Least Significant Bit): 1. Voltage output: 1LSB=10V/8000=2.5mV. | 2. Current output: 1LSB=20mA/4000=5µA. |
|
|
Explanation:
1. The content of CR#0 is model type, user can read the data from program to check if there is |
expansion module. |
2. CR#1 is used to set two internal channels working mode of analog output module. Every channel |
has four modes to set that can set individually. For example: if set CH1 to mode 2 (b2~b0=010), |
CH2 to mode 1(b5~b3=001). It needs to set CR#1 to H000A. The factory setting of CR#1 is H0000. |
3. CR#2 ~ CR#9, CR#12 ~ CR#21, CR#24 ~ CR#27 Reserved. |
4. CR #10 ~ CR#11 display CH1 and CH2 output signal. The setting range is K0~K4000. Factory |
setting is K0 and unit is LSB. |
5. R#22 ~ CR#23 means the value to adjust OFFSET value of CH1 and CH2. The factory setting is K0 |
and unit is LSB. If output value equal to 0 after calculating, the adjustable range of analog output |
voltage or current is |
Voltage adjustable range: |
Current adjustable range: |
6. R#28 ~ CR#29 means the value of adjust GAIN value of CH1 and CH2. The factory setting is K2000 |
and unit is LSB. If output value equal to 2000 after calculating, the adjustable range of analog output |
voltage or current is |
Voltage adjustable range: |
Current adjustable range: |
Please be noticed that GAIN VALUE – OFFSET VALUE = +400LSB ~+6000LSB (voltage or |
current). When this value within this range, the resolution of the output signal will be thin and the |
value variation will be larger. When this value exceeds this range, the resolution of output signal |
2.2Product Profile and Outline
|
|
| 4 |
|
|
|
| 5 |
|
1 | 3.00 | 25.20 | 60.00 | 6 |
|
| V+ |
| 7 |
|
| C |
| |
|
| I+ |
| |
|
|
| H |
|
|
| COM 1 |
| |
|
| FG |
| 8 |
|
| V+ | C | |
|
| I+ |
| |
|
|
| H | 10 |
|
| COM 2 |
FG
| 3.4 |
| 60.00 |
11 | 3.00 |
12 |
|
| 14 |
|
| 1 stop bit (8 E 1). The |
|
| connected in series with an MPU. |
| Connect to | If |
| numbered from 0 – 7. 0 is the closest and 7 is the furthest to the | |
| Series | MPU. 8 modules is the max and they do not occupy any digital I/O |
|
| points of the MPU. |
| 3.2 Other Specification |
|
will be thick and the variation of value will be smaller. |
7. CR#30 is the fault code. Please refer to the following chart. |
Fault Description | Content b15~b8 | b7 | b6 | b5 | b4 | b3 | b2 | b1 | b0 | |
Power Source Abnormal | K1(H1) | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | |
Analog Input Value Error | K2(H2) |
| 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 |
Setting Mode Error | K4(H4) |
| 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0 |
Offset/Gain Error | K8(H8) | Reserved | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 0 |
90.00
9
13 | 90.00 |
|
| 24 VDC (20.4VDC~28.8VDC) |
| Max. Rated Consuming Power | |
| external power | |
|
| |
|
|
|
|
|
|
Hardware Malfunction | K16(H10) | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0 |
| K32(H20) | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 |
2
3
3
Environment Condition and Wiring | Follow the |
Spec of Prevent Static Electricity | All places between terminals and ground comply with the spec |
Digital Range Error |
|
|
|
|
|
|
|
|
|
Average Times Setting Error | K64(H40) | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 |
Command Error | K128(H80) | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
4.00
Unit:mm
Note: Each fault code will have corresponding bit (b0~b7). Two or more faults may happen at the same time. 0 means normal and 1 means fault happened.