Desa CFS24NVC VS30N, B, C Mantel Clearances, Floor Clearances, Installation, Continued

Models: CFS24NVC VS30N B, C

1 30
Download 30 pages 50.94 Kb
Page 9
Image 9
MANTEL CLEARANCES

OWNER’S MANUAL

INSTALLATION

Continued

MANTEL CLEARANCES

In addition to meeting noncombustible mate- rial clearances, you must also meet required clearances between fireplace opening and mantel shelf. If you do not meet the clear- ances losted below, you will need a hood.

Determining Minimum Mantel Clearance

If you meet minimum clearance between mantel shelf and top of fireplace opening, a hood is not required (see Figure 6).

Determining Minimum Mantel Clearance When Using a Hood

If minimum clearances in Figure 6 are not met, you must have a hood. When using a hood there are still certain minimum mantel

Mantel Shelf

10"

Underside of

 

8"

 

 

 

 

 

 

Mantel Shelf

 

 

 

 

 

 

 

 

 

 

6"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 1/2"

 

 

 

 

 

 

All minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

distances are

Minimum Non-

 

 

(A)

 

 

 

 

 

 

in inches

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Combustible

 

 

 

 

 

 

 

 

Log Set

 

 

 

 

 

 

 

 

 

Material

 

 

 

 

 

 

 

 

 

 

 

12"

18"

 

20"

22"

24"

 

24"/30" Models

 

 

 

 

 

 

 

 

8"

14"

 

16 3/4"

18 1/2"

20"

 

18" Model

 

 

 

 

 

 

 

 

 

 

 

 

 

Top of Fireplace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Opening

 

 

Minimum Non-

Distances to

 

 

 

 

 

Combustible

 

Underside of

 

 

 

 

 

Material Height

Mantel

 

 

 

 

Figure 6 - Minimum Mantel Clearances Without Using Hood

clearances required. Follow minimum clear- ances shown in Figure 7 when using hood.

NOTICE: If your installation does not meet the minimum clearances shown, you must do one of the following:

operate the logs only with the flue damper open

raise the mantel to an accept- able height

remove the mantel

12"

10"

8"

6"

2 1/2"

Minimum Non-

Combustible

Material

Mantel Shelf

 

 

 

 

 

 

 

Underside of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mantel Shelf

 

 

 

 

 

 

 

All minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

distances are

 

 

 

 

 

 

 

in inches

 

 

 

 

 

 

 

 

Log Sets

8"

 

12"

15"

18"

20"

 

18", 24",

 

Min.

 

 

 

 

 

 

& 30" Models

 

 

 

 

 

 

 

 

 

Top of Fireplace

Opening

FLOOR CLEARANCES

A.If installing appliance on the floor level, you must maintain the minimum dis- tance of 14" to combustibles (see Fig- ure 8).

B.If combustible materials are less than 14" to the fireplace, you must install appliance at least 5" above the combus- tible flooring (see Figure 9).

Hood

Distances to

(GA6050, GA6052,

Underside of

or GA6053)

Mantel

Figure 7 - Minimum Mantel Clearances When Using Hood

 

Combustible

 

14"

Material

Hearth

 

Min.

 

 

Combustible

 

 

 

 

Material

 

 

5"

 

Noncombustible

Min.

 

Material

 

Figure 8 - Minimum Fireplace Clearances

Figure 9 - Minimum Fireplace Clearances

If Installed at Floor Level

 

Above Combustible Flooring

Continued

104414

9

Page 9
Image 9