Air Output, Air Intake, and Lint Filters

Air Output, Air Intake, and Lint Filters

1.Remove upper shell (see page 10).

2.Remove filter end cover screws using 5/16" nut- driver.

3.Remove filter end cover.

4.Replace air output and lint filters.

5.Wash or replace air intake filter (see Preventative Maintenance Schedule, page 8).

6.Replace filter end cover.

7.Replace fan guard and upper shell.

IMPORTANT: Do not oil filters

Pump Pressure

Adjustment

1.Remove pressure gauge plug from filter end cover.

2.Install accessory pressure gauge (part number HA1180).

3.Start heater (see Operation, page 7). Allow motor to reach full speed.

4.Adjust pressure. Turn relief valve to right to increase pressure. Turn relief valve to left to decrease pressure. See specifications at right for correct pressure for each model.

5.Remove pressure gauge. Replace pressure gauge plug in filter end cover.

14

Air Intake Filter

 

Filter End

 

Cover

Fan Guard

 

Lint Filter

Air Output

Filter

Figure 16 - Air Output, Air Intake, and Lint Filters,

30/70,000 Btu/Hr Models

Air Intake Filter

Filter End

Fan Guard

Cover

 

Lint Filter

Air Output

Filter

Figure 17 - Air Output, Air Intake, and Lint Filters,

90/150,000 Btu/Hr Models

(30/70,000 Btu/Hr Models Shown)

Pressure

Relief

Gauge

Valve

Plug

 

Figure 18 - Pressure Gauge Plug Removal

 

 

Pump

Pressure

 

 

Gauge

Model

Pressure

 

30,000

Btu/Hr

2.6 PSI

 

70,000

Btu/Hr

3.8 PSI

 

90,000

Btu/Hr

4.4 PSI

 

150,000

Btu/Hr

4.8 PSI

 

Figure 19 - Adjusting Pump Pressure