Desa CGB35P, CGB50P installation manual Fresh Air For Combustion And Ventilation, Continued

Models: CGB35P CGB50P

1 40
Download 40 pages 41.98 Kb
Page 19
Image 19
Example 2: Locating Heater in Confined (Closed) Area

FRESH AIR FOR COMBUSTION AND VENTILATION

Continued

Example 2: Locating Heater in Confined (Closed) Area

NOTICE

A confined area has an air volume of less than 50 cubic feet for each 1000 BTU/Hr input rating of all appliances in the area (cubic feet equals length x width x height of area). Include adjoining rooms only if there are no doors between the rooms.

If you install this heater in a confined area, you must provide additional fresh air.

Ventilating Confined Area

This fresh air would come from an adjoining open area or outdoors.

Manual background WARNING

The adjoining open area must have enough fresh, outside air ventilation to supply any appliance in that area plus the confined area. Follow instructions under Example 1: Locating Heater in Unconfined (Open) Area, page 17 to make sure fresh air ventilation is adequate.

When ventilating to an adjoining open area, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two areas. Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1. It lists fresh-air requirements for fuel-burning appliances.

Ventilation

Grills into

Closet for

Hot Water

Heater

12"

Ventilation Grills

Connecting Two Rooms to Meet Unconfined Space

12"

Recommended

Fresh Air Duct into Crawl Space in Furnace Area or in

Closet with Water Heater

Figure 15 - Ventilation Air from Inside Building

After providing ventilation between rooms, check for draft hood spillage (see Draft Hood Spillage Test, page 17). If draft hood spillage still occurs, provide more ventilation between rooms or provide permanent ventilation from outdoors. See Providing Permanent Fresh-Air Ventilation, page 18.

19