INSTALLATION
Checking Gas Connections
INSTALLATION
Continued
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.
WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.
CAUTION: Make sure external regulator has been installed between propane/LP supply and fireplace. See guidelines under Connecting to Gas Supply, page 14.
Pressure Testing Gas Supply Piping System
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1.Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping sys- tem. Pressures in excess of 1/2 psig will damage heater regulator.
2.Cap off open end of gas pipe where equipment shutoff valve was connected.
3.Pressurize supply piping system by either opening propane/ LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas, or using compressed air.
4.Check all joints of gas supply piping system. Apply a noncor- rosive leak detection fluid to gas joints. Bubbles forming show a leak.
5.Correct all leaks at once.
6.Reconnect heater and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1.Close equipment shutoff valve (see Figure 27).
2.Pressurize supply piping system by either opening propane/ LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas, or using compressed air.
3.Check all joints from gas meter for natural or propane/LP sup- ply to equipment shutoff valve (see Figures 28 and 29). Ap- ply a noncorrosive leak detection fluid to gas joints. Bubbles forming show a leak.
4.Correct all leaks at once.
Pressure Testing Fireplace Gas Connections
1.Open equipment shutoff valve (see Figure 27).
2.Open main gas valve located on or near gas meter for natural gas or open propane/LP supply tank valve.
3.Make sure control knob of fireplace is in the OFF position.
4.Check all joints from equipment shutoff valve to thermostat gas valve (see Figures 28 and 29). Apply a noncorrosive leak detection fluid to gas joints. Bubbles forming show a leak.
5.Correct all leaks at once.
6.Light fireplace (see Operating Fireplace, pages 17 and 18). Check all other internal joints for leaks.
7.Turn off fireplace (see To Turn Off Gas to Appliance, page 18).
8.Replace front panel.
Equipment | Open |
Shutoff |
|
Valve |
|
Closed
Figure 27 - Equipment Shutoff Valve
| Equipment |
Propane/LP | Shutoff Valve |
Supply Tank |
|
Figure 28 - Checking Gas Joints Shown with Optional Mantel (Propane/LP Gas)
Equipment Shutoff Valve
Gas Meter
Figure 29 - Checking Gas Joints Shown with Optional Mantel (Natural Gas)