INSTALLING

Continued

INSTALLING DAMPER CLAMP ACCESSORY FOR VENTED OPERATION

Note: When used as a vented heater, appliance must be installed only in a solid- fuel burning fireplace with a working flue and constructed of non combustible material.

If your heater is a manually controlled model, you may use this heater as a vented product. There are three reasons for operating your heater in the vented mode.

1.The fireplace does not meet the clearance to combustibles requirements for vent-free operation.

2.State or local codes do not permit vent-free operation.

3.You prefer vented operation.

If reasons number 1 or 2 above apply to you, you must permanently open chimney flue damper. You must install the damper clamp accessory (to order, see Accessories, page 29). This will insure vented operation (see Figure 10). The damper clamp will keep damper open. Installation instructions are included with clamp accessory.

See chart below for minimum permanent flue opening you must provide. Attach damper clamp so the minimum permanent flue opening will be maintained at all times.

Area of Various Standard Round Flues

Diameter (ins.)

Area (sq. ins.)

 

 

5"

20 sq. inches

6"

29 sq. inches

7"

39 sq. inches

8"

51 sq. inches

 

 

Chimney

Minimum Permanent

Height (ft.)

Flue Opening (sq. ins.)

 

 

6' to 15'

39 sq. inches

15' to 30'

29 sq. inches

 

 

Damper

Clamp

Damper

Damper

Clamp

Damper

Damper

Masonry Fireplace

Manufactured Fireplace

Figure 10 - Attaching Damper Clamp

102828

Continued