AIR FOR |
| WARNING ICONG 001WARNING |
|
| If the area in which the heater may be operated is smaller than |
| |
COMBUSTION |
|
| |
| that defined as an unconfined space, provide adequate combus- |
| |
AND |
| tion and ventilation air by one of the methods described in the |
|
| National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3. |
| |
VENTILATION |
|
| |
|
|
| |
VENTILATION AIR |
| ||
Continued |
| ||
Ventilation Air From Inside Building |
| ||
|
| ||
| This fresh air would come from an adjoining unconfined space. When ventilat- |
| |
| ing to an adjoining unconfined space, you must provide two permanent |
| |
| openings: one within 12" of the ceiling and one within 12" of the floor on the |
| |
| wall connecting the two spaces (see options 1 and 2, Figure 2). You can also |
| |
| remove door into adjoining room (see option 3, Figure 2). Follow the National |
| |
| Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and |
| |
| Ventilation for required size of ventilation grills or ducts. |
| |
|
|
|
|
|
| WARNING ICONG 001WARNING |
|
|
| Rework worksheet, adding the space of the adjoining unconfined |
|
|
| space. The combined spaces must have enough fresh air to supply all |
|
|
| appliances in both spaces. |
|
|
|
|
|
12"
| Ventilation Grills |
Ventilation | Into Adjoining Room, |
Option 2 | |
Grills | Or |
into Adjoining | Remove |
Room, | Door into |
Option 1 | Adjoining |
| Room, |
| Option 3 |
12"
Figure 2 - Ventilation Air from Inside Building
Continued | 7 |
|