Desa CGN18RA, CGN30D AIR for, Ventilation AIR, Ventilation Air From Inside Building

Models: CGN30D CGN18RA

1 32
Download 32 pages 61.11 Kb
Page 7
Image 7

AIR FOR

 

WARNING ICONG 001WARNING

 

 

If the area in which the heater may be operated is smaller than

 

COMBUSTION

 

 

 

that defined as an unconfined space, provide adequate combus-

 

AND

 

tion and ventilation air by one of the methods described in the

 

 

National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3.

 

VENTILATION

 

 

 

 

 

VENTILATION AIR

 

Continued

 

Ventilation Air From Inside Building

 

 

 

 

This fresh air would come from an adjoining unconfined space. When ventilat-

 

 

ing to an adjoining unconfined space, you must provide two permanent

 

 

openings: one within 12" of the ceiling and one within 12" of the floor on the

 

 

wall connecting the two spaces (see options 1 and 2, Figure 2). You can also

 

 

remove door into adjoining room (see option 3, Figure 2). Follow the National

 

 

Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and

 

 

Ventilation for required size of ventilation grills or ducts.

 

 

 

 

 

 

 

WARNING ICONG 001WARNING

 

 

 

Rework worksheet, adding the space of the adjoining unconfined

 

 

 

space. The combined spaces must have enough fresh air to supply all

 

 

 

appliances in both spaces.

 

 

 

 

 

12"

 

Ventilation Grills

Ventilation

Into Adjoining Room,

Option 2

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12"

Figure 2 - Ventilation Air from Inside Building

Continued

7

 

101826

Page 7
Image 7
Desa CGN18RA, CGN30D AIR for, Ventilation AIR, Ventilation Air From Inside Building, Appliances in both spaces