INSTALLATION

Continued

Minimum Clearances For Side Combustible Material, Side Wall, and Ceiling

A.Clearances from the side of the fireplace cabi- net to any combustible material and wall should follow diagram in Figure 6.

Example: The face of a mantel, bookshelf, etc. is made of combustible material and pro- trudes 3 1/2" from the wall. This combustible material must be 4" from the side of the fire- place opening (see Figure 6).

B.Clearances from the top of the fireplace opening to the ceiling should not be less than 36 inches.

C.For mantel clearances, see Figure 10 on page 12.

MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS

Top

Left and

Bottom

 

Right Sides

and Rear

36"

6"

0"

 

Example

 

 

 

*

*Minimum 16 inches from Side Wall

Figure 6 - Minimum Clearance for

Combustible to Wall

BUILT-IN FIREPLACE

INSTALLATION

Built-in installation of this fireplace involves in- stalling fireplace into a framed-in enclosure. This makes the front of fireplace flush with wall. An optional trim kit accessory is available (see Ac- cessories, page 40). Trim will extend past sides of fireplace approximately 1/2 inch. This will cover the rough edges of the wall opening. If installing a built-in mantel above the fireplace, you must follow the clearances shown in Figure 10, page

11.Follow the instructions below to install the fire- place in this manner.

 

Actual

Framing

Height

26"

26 7/8"

Front Width

26 3/4"

26 7/8"

Depth

9 1/2"

10 1/2"

Bottom

3/4"

3/4"

1.Frame in rough opening. Use dimensions shown in Figure 7 for the rough opening. If installing in a corner, use dimensions shown in Figure 8 for the rough opening. The height is 26 7/8" which is the same as the wall opening above.

2.If installing GA3450T blower accessory, do so at this time. Follow instructions included with blower accessory.

Note: If not installing blower accessory, you may wish to run electrical wiring to your fire- place for future blower installation (see Ac- cessories, page 40). Use only approved three- wire electrical wiring.

WARNING: If pre-wiring, do not connect wiring to any elec- trical source at this time.

Install fireplace electrical outlet and connect wiring to outlet be- fore connecting to electrical source. The fireplace electrical outlet is included with the GA3450T blower accessory.

Only use the fireplace electrical outlet supplied with the GA3450T blower accessory.

Note: A qualified installer should make all elec- trical connections.

101/2"

267/8"

3/4" Off

The Floor

267/8" Minimum

Figure 7 - Rough Opening for Installing

in Wall

365/8"

257/8"

267/8" 513/4"

Figure 8 - Rough Opening for Installing

in Corner

112462-01B

www.desatech.com

11

Page 11
Image 11
Desa VMH10TPC, EFS10TNA, EFS10TPA Minimum Clearance to Combustible Materials, BUILT-IN Fireplace Installation, Example