Installation
Continued
For propane/LP units, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11" and 14" of water. If you do not reduce incoming gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure
17.Pointing the vent down protects it from freezing rain or sleet.
CAUTION: Use only new, black iron or steel pipe. Internally
Installation must include an equipment shutoff valve, union and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up.
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fireplace valves. Never use sealant on flare threads.
WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
We recommend that you install a sediment trap in supply line as shown in Figure 18. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and fireplace. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into fireplace gas controls. If sediment trap is not installed or is installed wrong, fireplace may not run properly.
CSA
NPT tap must be upstream from fireplace (see Figure 18).
IMPORTANT: Install equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.
Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.
3" Minimum
Natural Gas From Gas Meter (5" W.C.** to
10.5" W.C. Pressure)
Propane/LP
From External
Regulator
(11" W.C.** to 14" W.C.
Pressure)
External Regulator
Propane/LP Supply Tank
Cap
Pipe Tee Nipple Joint
Sediment Trap
Figure 18 - Gas Connection
Vent
Pointing
Down
Figure 17 - External Regulator on Propane/LP Supply Tank with Vent Pointing Down
*Purchase the optional CSA
** Minimum inlet pressure for purpose of input adjustment.
14 | www.desatech.com |