PORTABLE GASOLINE GENERATORS

DETERMINING ELECTRICAL LOAD FOR GENERATOR

You must decide what electrical load your generator can power. Do this before us- ing generator. Use the following four-step method. It will help you select a load that is not too large. Make sure total wattage of all electrical loads does not exceed rated wattage of generator. For rated wattage of your generator, see Specifications, page 5. Electric motors present a special problem when figuring load. Read Step 3 carefully.

1.Make two lists of items you want pow- ered by generator. List all motors and motor powered appliances in one. List all lights, small appliances, etc. in the other. For standby service to home or building, only include items you must power.

2.Enter running watts of each item except motors. The light bulb or appliance nameplate lists its wattage. Remem- ber, 1KW = 1000 watts. Note: The nameplate may not list wattage. It may only list volts and amps. The formula for finding wattage is: Volts x Amps = Watts. For example: An appliance nameplate states 3 amps at 120 volts. 3 amps x 120 volts = 360 watts.

3.Electric motors present a special prob- lem. They require up to three-times their rated wattage to start. Chart 2, below, shows starting watts for different size motors. For example: an electric motor nameplate states 5 amps at 120 volts. 5 amps x 120 volts = 600 watts running. Multiply this figure by 3. This will show the starting watts needed. 600 watts x 3 = 1800 watts to start. When figuring the generator load for motors, you must use the starting watts figure.

Do not use the running watts figure. Note: Some motors require nearly the same wattage to run as to start. These items include saws, drills, hair dryers, and food mixers. See Chart 1 for typical appliance wattage examples.

4.Add watts and starting watts of all items. This total must not be larger than the rated wattage of your generator. It is a good idea to have up to 25% extra capacity for future needs or extra equipment.

Typical Electric Appliance Wattages

Chart 1

 

Running

Starting

Equipment

Watts

Watts

 

 

 

Light bulb (100W)

100

100

Radio

150

150

Fan

 

 

200

600

Television

 

 

400

400

Furnace fan (1/3 hp)

 

 

600

1800

with blower

 

 

Vacuum cleaner

 

 

600

750

Sump pump (1/3 hp)

 

 

700

2100

Refrigerator/freezer

 

 

800

2400

6" Circular saw

 

 

800

1000

Floodlight

 

 

1000

1000

1/2" Drill

 

 

1000

1250

Toaster

 

 

1200

1200

Coffee maker

 

 

1200

1200

Skillet

 

 

1200

1200

14" Chain saw

 

 

1200

1500

Water well pump

 

 

1000

3000

(1/2 hp)

 

 

Hot plate/range

 

 

1500

1500

(per burner)

 

 

10" Table saw

 

 

2000

6000

Water heater

 

 

5000

5000

(storage-type)

 

 

Chart 2

 

 

Approximate Starting Watts*

 

 

 

 

 

 

 

Motor

Approximate

Universal

Repulsion

 

Split

HP

Running

Motors

Induction

Capacitor

Phase

Rating

Watts

(small appliance)

Motors

Motors

Motors

 

 

 

 

 

 

1/8

500

625

1100

1500

2250

1/4

 

875

1550

2100

3150

700

1/3

 

1000

1750

2400

3600

800

1/2

 

1375

2400

3300

4950

1100

3/4

 

1750

3100

4200

x

1400

1

 

2125

3750

5100

x

1700

1 1/2

 

2625

4620

6300

x

2100

2

 

3075

5400

7350

x

2450

3

 

x

7900

10800

x

3600

 

 

 

 

 

 

*– Always use starting watts, not running watts, when figuring correct electrical load. x – Motors of higher horsepower are not generally used.