Figure 13 - Flashing Installation

Venting Installation

Continued

Storm

Overlap

Collar

Shingles Top

Flashing

and Sides Only

Cone

 

Nail Only

 

Outer

 

Perimeter

 

of Flashing

 

Underlap

Shingles

at Bottom

Figure 13 - Flashing Installation

Installing Flashing on a Metal Roof

When installing the flashing on a metal roof, it is required that putty tape be used between the flash- ing and the roof. The flashing must be secured to the roof using #8 x 3/4" screws and then sealed with roof coating to prevent leakage through the screw holes. A roof coating must also be applied around the perimeter of the flashing to provide a proper seal.

Storm Collar Installation (SC2-1)

Place storm collar over pipe and slide down until it is snug against the open edge of the flashing (see Figure 14). Apply waterproof caulk around the perimeter of the collar to provide a proper seal.

Chimney

Waterproof

Pipe

Caulk

Storm

Flashing

Collar

Figure 15 - Termination CAUTION: Do not seal open- ings on the rooftop flashing. Fol- low the installation instructions provided with the termination being used.

 

RTL-10D

Stainless

Level of

Inner Flue

Flue Gas

Pipe

Outlet

 

Secure

 

Termination

Waterproof

to Outer

Pipe with 3

Caulking

Screws

Storm

 

Collar

 

Flashing

Overlap

Underlap

Shingles (Top and Sides

Shingles

of Flashing Base)

 

Figure 15 - Termination

Chase installations

Instructions for chase installations are included with the chase style termination chosen. In a multiple chase installation, be sure to provide adequate distance between terminations to prevent smoke spillage from one termination to another. We suggest that terminations be separated at least 24" center to center and stacked at a vertical height difference of 18" (see Figure 16, page 11).

Note: If a decorative shroud is to be installed, contact the manufacturer for specifications.

Figure 14 - Storm Collar

Terminations/Spark Arrestor

The fireplace system must be terminated with the listed round top or chase terminations. In any case, refer to the installation instructions supplied with the termination.

18"

Min.

Typ.

24" Min.

24" Min.

Figure 16 - Multiple Chase Installation