AIR FOR COMBUSTION AND VENTILATION

Providing Adequate Ventilation (Cont.) Determining Fresh-Air Flow for Heater Location

5

AIR FOR COMBUSTION AND VENTILATION

Continued

c.caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.

If your home meets all of the three criteria (a,b, and c, you must provide additional fresh air. See Ventila- tion Air From Outdoors, page 6.

If your home does not meet all of the three criteria above, proceed to Determining Fresh-Air Flow For Heater Location.

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.

*Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height). Length x Width x Height = ___________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maximum Btu/Hr the space

can support)

Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

_____________ Btu/Hr

Gas water heater*

 

_____________ Btu/Hr

Gas furnace

 

_____________ Btu/Hr

Vented gas heater

 

_____________ Btu/Hr

Gas fireplace logs

 

_____________ Btu/Hr

Other gas appliances* +

_____________ Btu/Hr

Total

=

_____________ Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws com- bustion air from the outdoors and vents to the outdoors.

Example:

Gas water heater

 

40,000

Btu/Hr

Vent-free heater

+

33,000

Btu/Hr

Total

=

73,000

Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/ Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Out- doors, page 6.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an uncon- fined space or if the building is of unusually tight construction, provide adequate combustion and ven- tilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec- tion 5.3 or applicable local codes.

For morevisit www..com

111515-01C

Page 5
Image 5
Desa LDL3924PR, LDL3930PR, LDL3930NR Determining FRESH-AIR Flow for Heater Location, Confined and Unconfined Space

LDL3924PR, LDL3930NR, LDL3930PR specifications

Desa LDL3924PR, LDL3930PR, and LDL3930NR represent a comprehensive range of innovative HVAC solutions. Each model is engineered to provide efficient heating and cooling in residential and commercial applications, ensuring optimal thermal comfort throughout the year.

The LDL3924PR model stands out with its advanced inverter technology, enabling variable speed operation that adjusts according to the heating or cooling demand. This not only enhances energy efficiency but also promotes quieter operation, making it ideal for residential settings. By seamlessly adapting to temperature fluctuations, users experience consistent comfort without the energy spikes often associated with conventional systems.

Similarly, the LDL3930PR model incorporates robust features such as high SEER (Seasonal Energy Efficiency Ratio) ratings, which indicate superior energy efficiency during cooling cycles. This model is specifically designed to work efficiently even in extreme weather conditions, maintaining performance in both high temperatures and colder climates. The extended lifespan of the compressor is another hallmark, thanks to its advanced protection mechanisms and durable construction materials.

The LDL3930NR is particularly notable for its eco-friendly refrigerant, which significantly reduces greenhouse gas emissions while maintaining excellent cooling efficiency. This model focuses on sustainable cooling solutions, aligning with global initiatives to combat climate change. With a sleek design, it blends seamlessly into modern spaces, making it a popular choice for aesthetic-conscious consumers.

All three models boast user-friendly interfaces, enabling easy control and customization of settings. Smart capabilities are integrated into the design, allowing for remote access and monitoring via mobile applications. This feature empowers users to adjust settings from anywhere, optimizing energy usage and ensuring comfort is always within reach.

In addition, these models include multi-stage filtration systems that not only enhance indoor air quality but also reduce allergens and pollutants. With low operating noise levels and aesthetically pleasing designs, the Desa LDL series is capable of enhancing any environment while promoting energy efficiency.

Whether for residential or commercial use, Desa's LDL3924PR, LDL3930PR, and LDL3930NR models exemplify the perfect integration of technology, efficiency, and user-centric design principles, making them top choices in the modern HVAC market.