UNVENTED NATURAL GAS FIREPLACE

INSTALLATION

Continued

CHECKING GAS

CONNECTIONS

WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1. Disconnect appliance with its appliance

main gas valve (control valve) and

equipment shutoff valve from gas sup-

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Fig- ure 19).

2.Pressurize supply piping system by ei- ther using compressed air or opening main gas valve located on or near gas meter.

3.Check all joints from gas meter to equipment shutoff valve (see Figure 20). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Open

Equipment

Shutoff

Valve

Closed

Figure 19 - Equipment Shutoff Valve

Pressure Testing Fireplace Gas Connections

1.Open equipment shutoff valve (see Fig- ure 19).

2.Open main gas valve located on or near gas meter.

3.Make sure control knob of fireplace is in the OFF position.

4.Check all joints from equipment shutoff valve to thermostat gas valve (see Fig- ure 20). Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

5.Correct all leaks at once.

6.Light fireplace (see Operating Fire- place, pages 16 and 17). Check all other internal joints for leaks.

7.Turn off fireplace (see To Turn Off Gas to Appliance, page 17).

 

ply piping system. Pressures in excess

 

of 1/2 psig will damage fireplace gas

 

regulator.

2.

Cap off open end of gas pipe where

 

equipment shutoff valve was connected.

3.

Pressurize supply piping system by ei-

 

ther using compressed air or opening

 

main gas valve located on or near gas

 

meter.

4.

Check all joints of gas supply piping

 

system. Apply mixture of liquid soap

 

and water to gas joints. Bubbles form-

 

ing show a leak.

5.

Correct all leaks at once.

6.

Reconnect fireplace and equipment

 

shutoff valve to gas supply. Check re-

 

connected fittings for leaks.

Manual Gas Valve

Figure 20 - Checking Gas Joints

Equipment

Shutoff

Valve

Gas Meter

12