TROUBLESHOOTING

Continued

WARNING: If you smell gas

Shut off gas supply.

Do not try to light any appliance.

Do not touch any electrical switch; do not use any phone in your building.

Immediately call your gas supplier from a neighbor’s phone. Fol- low the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

IMPORTANT: Operating heater where impurities in air exist may create odors. Cleaning supplies, paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles, etc., create fumes. These fumes may mix with combustion air and create odors.

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

 

 

 

 

 

Heater produces unwanted

1.

Heater burning vapors from

1.

Ventilate room. Stop using

odors

 

paint, hair spray, glues, etc.

 

odor causing products while

 

 

(see IMPORTANT statement

 

heater is running

 

 

above)

2.

Refill supply tank

 

2.

Low fuel supply

 

3.

Gas leak. See Warning

3.

Locate and correct all leaks

 

 

statement above

 

(see Checking Gas Connec-

 

 

 

 

tions for Permanent Gas Sup-

 

 

 

 

ply, page 10)

 

 

 

 

 

Heater shuts off in use (ODS

1.

Not enough fresh air is

1.

Open window and/or door for

operates)

 

available

 

ventilation

 

2.

Low line pressure

2.

Contact local propane/LP gas

 

3.

O D S / p i l o t i s p a r t i a l l y

 

company

 

3.

Clean ODS/pilot (see Cleaning

 

 

clogged

 

and Maintenance, page 13)

 

 

 

 

 

Gas odor even when control knob

1.

Gas leak. See Warning

1.

Locate and correct all leaks

is in OFF position

 

statement above

 

(see Checking Gas Connec-

 

 

 

 

tions for Permanent Gas Sup-

 

 

 

 

ply, page 10)

 

2.

Control valve defective

2.

Replace control valve

 

 

 

 

 

Gas odor during combustion

1.

Foreign matter between con-

1.

Take apart gas tubing and

 

 

trol valve and burner

 

remove foreign matter

 

2.

Gas leak. See Warning

2.

Locate and correct all leaks

 

 

statement above

 

(see Checking Gas Connec-

 

 

 

 

tions for Permanent Gas Sup-

 

 

 

 

ply, page 10)

 

 

 

 

 

Moisture/condensation noticed

1.

Not enough combustion/ven-

1.

Provide more combustion

on windows

 

tilation air

 

area. A minimum 10 square

 

 

 

 

inches of ventilation air must

 

 

 

 

be provided for adequate

 

 

 

 

combustion

16