Desa RL24NR, CTB3924NT Installation, Continued, Minimum Noncombustible Material Clearances

Models: RL24NR CSG3924PT CSG3924PR VRL30PR CTB3924NT

1 38
Download 38 pages 2.89 Kb
Page 9
Image 9
8". See Between 8" and 12",

INSTALLATION

Installation and Clearances For Vent-Free Operation (Cont.)

9

INSTALLATION

Continued

Carefully follow the instructions below. This will ensure safe installation into a masonry, UL127-listed manufactured fireplace, or listed vent-free firebox.

Minimum Clearances For Side Combustible Material, Side Wall, and Ceiling

A.Clearances from the side of the fireplace cabinet to any com- bustible material and wall should follow diagram in Figure 4.

Example: The face of a mantel, bookshelf, etc. is made of combustible material and protrudes 3 1/2" from the wall. This combustible material must be 4" from the side of the fireplace cabinet (see Figure 4).

Note: When installing your gas logs into a manufactured firebox, follow firebox manufacturer’s instructions for minimum clear- ances to combustible materials.

B.Clearances from the top of the fireplace opening to the ceiling should not be less than 42 inches.

Example

*

*Minimum 16 inches from Side Wall

Figure 4 - Minimum Clearance for Combustible to Wall

If Using Mantel

You must have noncombustible material(s) above the fireplace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombustible material must extend at least 8 inches up. If noncombustible material is less than 12", you must install the fireplace hood accessory. Even if noncom- bustible material is more than 12", you may need the hood accessory to deflect heat away from your mantel shelf. See Figure 5 and Figures 6 and 7, page 10, for minimum clearances.

IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open. Go to Install- ing Damper Clamp Accessory for Vented Operation, page 11.

Noncombustible

Requirements for

Material Distance (A)

Safe Installation

 

 

12" or more

Noncombustible material OK.

Between 8" and 12"

24" or 30" Models: Install

 

fireplace hood accessory

 

(GA6050, GA6052, or

 

GA6053 see Accessories,

 

page 34).

Less than 8"

Noncombustible material

 

must be extended to at least

 

8". See Between 8" and 12",

 

above. If you cannot extend

 

material, you must operate

 

heater with flue damper open.

 

 

NOTICE: Manual control heaters may be used as a vented product. If so, you must always run heater with chimney flue damper open. If running heater with damper open, noncombustible material above fire- place opening is not needed. Go to Installing Damper Clamp Accessory for Vented Operation, page 11.

Heat Resistant Minimum Noncombustible Material Clearances

Material

(A)

Minimum Noncombustible Material Clearances

If Not Using Mantel

Note: If using a mantel proceed to If Using Mantel. If not using a mantel, follow the information on this page.

You must have noncombustible material(s) above the fireplace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombustible material must extend at least 8" up (for all models). If noncombustible material is less than 12", you must install the fireplace hood accessory (24" and 30" models only). See Figure 5 for minimum clearances.

Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.) Above Fireplace

Manual backgroundFor moreManual backgroundManual backgroundManual backgroundvisit www.Manual backgroundManual backgroundManual background.comManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

110021-01C

Page 9
Image 9
Desa RL24NR, CTB3924NT, CSG3924NR Installation, Continued, Minimum Noncombustible Material Clearances, See Between 8 and