DETERMINING FRESH-AIR FLOW FOR APPLIANCE LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install appliance plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = ____________________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

________________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

CO2 generator

 

______________________ Btu/Hr

 

 

 

Gas water heater*

 

Example:

 

 

 

 

______________________ Btu/Hr

 

40,000

Btu/Hr

 

 

Gas water heater

 

Gas furnace

 

______________________ Btu/Hr

+

 

 

 

30,000

Btu/Hr

 

 

CO2 generator

Vented gas heater

 

______________________ Btu/Hr

=

 

 

 

 

 

 

+

Total

70,000

Btu/Hr

Other gas appliances*

______________________ Btu/Hr

 

 

 

 

 

 

Total

=

______________________ Btu/Hr

 

 

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_____________ Btu/Hr (maximum the space can support)

_____________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 70,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 5.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 5.

C.Install a lower Btu/Hr appliance, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the CO2 generator may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3, Canadian Gas Code B-149.1 and 2-M95, Section 7.2 and 7.3, or applicable local codes.

Continued

4

105056

Page 4
Image 4
Desa RP30E-CAN, RN30E-CAN AIR for Combustion Ventilation, Determining FRESH-AIR Flow for Appliance Location

RP30E-CAN, RN30E-CAN specifications

Desa RN30E-CAN and RP30E-CAN are cutting-edge compact portable generators that stand out in the market for their versatility and efficiency. Designed for a variety of applications, from camping trips to emergency power supply, these generators provide reliable performance in a compact format.

One of the key features of the RN30E-CAN and RP30E-CAN is their robust engine design. Powered by advanced gasoline engines, both models offer impressive starting capabilities and sustained power output. The RN30E-CAN produces a maximum output of 3,000 watts, while the RP30E-CAN takes it a step further with a peak output of 3,500 watts. This makes them ideal choices for powering essential devices, ranging from small appliances to larger equipment.

Efficiency is another hallmark of these generators. With a focus on fuel economy, both models incorporate innovative technologies that minimize fuel consumption while maximizing power. This not only helps save money but also reduces the environmental footprint of the generators. Users can take advantage of extended run times, making them perfect for longer outings or during unexpected outages.

In terms of user-friendly design, both RN30E-CAN and RP30E-CAN generators come equipped with intuitive control panels that simplify operation. The clear layout allows users to monitor power output and fuel levels effortlessly. Additionally, their lightweight construction, paired with integrated wheels and handles, enhances portability, making them easy to transport to any location.

Safety features are paramount in the design of the RN30E-CAN and RP30E-CAN. Equipped with automatic shutdown functions in the event of low oil levels and overload protection circuits, they provide peace of mind to users. The generators also boast a weather-resistant casing, ensuring durability and reliability even in adverse conditions.

Finally, both models are designed with noise reduction technology, making them quieter than many traditional generators. This makes them suitable for use in residential areas and during nighttime hours, allowing users to enjoy the benefits of portable power without disturbing their surroundings.

In summary, the Desa RN30E-CAN and RP30E-CAN generators combine power, efficiency, and safety into compact units that meet the needs of diverse users. Their advanced technology, ease of use, and portability make them excellent choices for anyone seeking reliable power on the go.