MANTEL CLEARANCES

INSTALLATION

Continued

MANTEL CLEARANCES

In addition to meeting noncombustible material clearances, you must also meet required clearances between fireplace opening and mantel shelf. If you do not meet the clearances listed below, you will need a hood.

Determining Minimum Mantel Clearance If you meet minimum clearance between mantel shelf and top of fireplace opening, a hood is not required (see Figure 6).

Determining Minimum Mantel Clearance When Using a Hood

If minimum clearances in Figure 6 are not met, you must have a hood. When using a hood there are still certain minimum mantel clearances required. Follow minimum clearances shown in Figure 7 when using hood.

NOTICE: Surface temperatures ofadjacentwallsandmantelsbe- comehotduringoperation.Walls and mantels above the firebox may become hot to the touch. If installed properly, these tem- peratures meet the requirement of the national product standard. Follow all minimum clearances shown in this manual.

NOTICE: If your installation does not meet the minimum clear- ances shown, you must do one of the following:

• operate the logs only with the

flue damper open and damper

clamp installed

 

10"

 

8"

 

 

6"

 

 

2 1/2"

Minimum Non-

 

 

(A)

 

 

 

 

Combustible

 

 

 

 

 

Material

 

 

12"

 

 

 

 

 

 

8"

 

 

 

 

Mantel Shelf

18"

 

20"

22"

 

14"

 

17"

19"

 

 

 

 

Underside of

Mantel Shelf

All minimum distances are in inches

Log Set

24" • operate the logs only with the 24" Models

20" FLOOR CLEARANCES 18" Model

Top of Fireplace

Opening

raise the mantel to an ac-

 

ceptable height

remove the mantel

FLOOR CLEARANCES

A.

If installing appliance on the floor level, you

 

must maintain the minimum distance of 14"

 

to combustibles (see Figure 8).

B.

If combustible materials are less than 14" to

Minimum Non-

Distances to

Combustible

Underside of

Material Height

Mantel

the fireplace, you must install appliance at

least 5" above the combustible flooring (see

Figure 9).

Figure 6 - Minimum Mantel Clearances

Without Using Hood

12"

10"

8"

6"

2 1/2"

Minimum Non-

 

Combustible

8"

Material

 

Min.

Hood (GA6050, GA6052 or GA6053)

 

12"

 

15"

18"

 

 

 

 

 

 

 

 

 

Distances to

Underside of

Mantel

 

 

 

Combustible

Underside of

14"

Material

 

Min.

 

Mantel Shelf

 

 

All minimum

 

 

 

distances are

 

Noncombustible

 

in inches

 

 

 

Material

 

Log Sets

 

20"

Figure 8 - Minimum Fireplace Clearances

18", 24" Models

 

Top of Fireplace

If Installed at Floor Level

 

Opening

 

Figure 7 - Minimum Mantel Clearances

Hearth

Combustible

When Using Hood

 

 

Material

 

5"

 

 

Min.

 

 

Figure 9 - Minimum Fireplace Clearances

 

Above Combustible Flooring

114744-01B

www.desatech.com

11

Page 11
Image 11