INSTALLATION

NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your pri- mary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.

WARNING: A qualified ser- vice person must install fire- place. Follow all local codes.

WARNING: Never install the heater

in a bedroom or bathroom

in a recreational vehicle

where curtains, furniture, clothing, or other flammable objects are less than 42 inches from the front, top, or sides of the heater

in high traffic areas

in windy or drafty areas

CAUTION: This heater cre- ates warm air currents. These currents move heat to wall sur- faces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as, but not limited to, tobacco smoke, aromatic candles, cleaning flu- ids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.

IMPORTANT: Vent-free heaters add moisture to the air. Although this is beneficial, installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and Ventilation, page 5.

CHECK GAS TYPE

Use only the correct type of gas (natural or pro- pane/LP). If your gas supply is not the correct gas type, do not install heater. Call dealer where you bought heater for proper type heater.

WARNING: This appliance is equipped for (natural or pro- pane/LP) gas. Field conversion is not permitted.

CLEARANCES TO COMBUSTIBLES

WARNING: Maintain the minimum clearances. If you can, provide greater clearances from floor, ceiling, and adjoining side and back walls.

Carefully follow the instructions below. This stove is a freestanding unit designed to set directly on the floor. IMPORTANT: You must maintain mini- mum wall and ceiling clearances during installa- tion. The minimum clearances are shown in Fig- ure 4, page 9. Measure from outermost point of stove top.

Minimum Wall and Ceiling Clearances (see Figure 4, page 9)

A.Clearances from outermost point of stove top to any combustible side wall should not be less than 12 inches.

B.Clearances from outermost point of stove top to any combustible back wall should not be less than 6 inches (includes corner installa- tions).

C.Clearances from the stove top to the ceiling should not be less than 48 inches.

8

www.desatech.com

113084-01C

Page 8
Image 8
Desa SVYD18PRA Installation, Check GAS Type, Clearances to Combustibles, Minimum Wall and Ceiling Clearances see