INSTALLING

The installer must supply an external regulator. The external regulator will reduce

incoming gas pressure. You must reduce incoming gas pressure to between 11 and

 

Continued

14 inches of water. If you do not reduce incoming gas pressure, heater regulator

 

damage could occur. Install external regulator with the vent pointing down as

 

shown in Figure 13. Pointing the vent down protects it from freezing rain or sleet.

 

Propane

 

Supply Tank

 

 

 

 

 

External

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Regulator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vent Pointing

Down

Figure 13 - External Regulator With Vent Pointing Down

WARNING

WARNING ICON

G 001

Never connect heater to private (non-utility) gas wells. This gas is commonly known as well-head gas.

CAUTION

WARNING ICON

G 001

Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diameter or greater to allow proper gas volume to heater. If pipe is too small, undue loss of pressure will occur.

Installation must include a manual shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 14, page 18).

Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.

CAUTION

WARNING ICON

G 001

Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

Install sediment trap in supply line as shown in Figure 14, page 18. Locate sedi- ment trap where it is within reach for cleaning. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.