INSTALLING | The installer must supply an external regulator. The external regulator will reduce | |||||||
incoming gas pressure. You must reduce incoming gas pressure to between 11 and | ||||||||
| ||||||||
Continued | 14 inches of water. If you do not reduce incoming gas pressure, heater regulator | |||||||
| damage could occur. Install external regulator with the vent pointing down as | |||||||
| shown in Figure 13. Pointing the vent down protects it from freezing rain or sleet. | |||||||
| Propane | |||||||
| Supply Tank |
|
|
|
|
| External | |
|
| |||||||
|
|
|
|
|
| |||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| Regulator | |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
Vent Pointing
Down
Figure 13 - External Regulator With Vent Pointing Down
WARNING
WARNING ICON | G 001 |
Never connect heater to private
CAUTION
WARNING ICON | G 001 |
Use only new, black iron or steel pipe.
Installation must include a manual shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 14, page 18).
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.
CAUTION
WARNING ICON | G 001 |
Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
Install sediment trap in supply line as shown in Figure 14, page 18. Locate sedi- ment trap where it is within reach for cleaning. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.
Continued 17