INSTALLATION

Continued

INSTALLING DAMPER CLAMP ACCESSORY FOR VENTED OPERATION

Note: When used as a vented decorative, appliance must be installed only in a solid-fuel burning fireplace with a working flue and constructed of noncombustible material.

If your heater is a non-thermostatically-controlled model, you may use this heater as a vented product. There are three reasons for operating your heater in the vented mode.

1.The fireplace does not meet the clearance to combustibles requirements for vent-free operation.

2.State or local codes do not permit vent-free operation.

3.You prefer vented operation.

If reasons number 1 or 2 above apply to you, you must permanently open chimney flue damper. You must install the damper clamp accessory (to order, see Accessories, page 26). This will insure vented operation (see Figure 10). The damper clamp will keep damper open. Installation instructions are included with clamp accessory.

Damper

Damper

Clamp

 

Damper

Damper

Clamp

Damper

Masonry Manufactured

FireplaceFireplace

Figure 10 - Attaching Damper Clamp

See chart below for minimum permanent flue

opening you must provide. Attach damper clamp

so the minimum permanent flue opening will be

maintained at all times.

 

Area of Various Standard

Round Flues

Diameter (ins.)

Area (sq. ins.)

5"

20 sq. inches

6"

29 sq. inches

7"

39 sq. inches

8"

51 sq. inches

Chimney

Minimum Permanent

Height (ft.)

Flue Opening (sq. ins.)

6' to 15'

39 sq. inches

15' to 30'

29 sq. inches

INSTALLING HEATER ASSEMBLY

WARNING: If installing in a

sunken fireplace, special care

is needed. You must raise the

fireplace floor to allow access

to heater control panel. This

will insure adequate air flow and

guard against sooting. Raise

fireplace floor with noncombus-

tible material. Make sure material

is secure.

 

CAUTION: Do not pick up

heater assembly by logs. This

could damage unit. Only handle

assembly by grates.

IMPORTANT: Make sure the heater burners are

level. If heater is not level, heater will not work

properly.

 

Installation Items Needed

control cover kit (provided with heater)

approved flexible gas hose and fittings (pro- vided with heater) (if allowed by local codes)

sealant (resistant to propane/LP gas, not provided)

12