AIR FOR COMBUSTION

AND VENTILATION

Continued

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2,560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maxi- mum Btu/Hr the space can support)

Example: 2,560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free fireplace

__________ Btu/Hr

Gas water heater*

__________ Btu/Hr

Gas furnace

__________ Btu/Hr

Vented gas heater

__________ Btu/Hr

Gas fireplace logs

__________ Btu/Hr

Other gas appliances*

+ ________ Btu/Hr

Total

= ________ Btu/Hr

*Do not include direct-vent gas appliances. Di- rect-vent draws combustion air from the outdoors and vents to the outdoors.

Example:

40,000

Gas water heater

__________ Btu/Hr

Vent-free fireplace

39,000

+ ________ Btu/Hr

Total

79,000

= ________ Btu/Hr

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an un- confined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be oper- ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA54 Section 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two perma- nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________ Btu/Hr (maximum the space can support)

_________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support)

79,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the example is a confined space because the actual Btu/Hr used is more than the maximum

Ventilation

 

Grills

 

Into Adjoining

Or

Room,

Remove

Option 1

Door into

 

 

Adjoining

 

Room,

 

Option

 

3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

Btu/Hr the space can support. You must provide ad- ditional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoin- ing room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ventila- tion Air From Outdoors, page 8.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

12"

Figure 2 - Ventilation Air from Inside

Building

112882-01D

www.desatech.com

7

Page 7
Image 7
Desa VGL18NRA, VGL30PRA installation manual Ventilation AIR, Ventilation Air From Inside Building

VGL18NRA, VGL30PRA, VGL18NRA, VGL18PRA, VGL24NRA, VGL24PRA, VGL30NRA, VGL30PRA specifications

Desa VGL series offers a range of innovative and efficient lighting solutions, primarily catering to various lighting needs in residential and commercial spaces. The models VGL18NRA, VGL18PRA, VGL24NRA, VGL24PRA, VGL30NRA, and VGL30PRA have been designed to provide high-performance lighting while maintaining energy efficiency.

Each model in the Desa VGL lineup features a robust design, making them suitable for diverse environments. The VGL18NRA and VGL18PRA models are known for their compact size, making them ideal for smaller spaces while still delivering powerful illumination. These models utilize advanced LED technology, ensuring a longer lifespan and lower energy consumption compared to traditional lighting solutions.

In contrast, the VGL24NRA and VGL24PRA models offer a step up in brightness and area coverage, making them perfect for medium-sized settings. With enhanced lumen output and superior optical design, these lights can effectively illuminate larger areas, ensuring safety and visibility.

The VGL30NRA and VGL30PRA models harness cutting-edge features, providing maximum brightness and adaptability for larger commercial spaces. These models come equipped with smart technologies, including dimming options and motion sensors, allowing for customized lighting solutions based on specific needs. This makes them an excellent choice for dynamic environments where lighting requirements may change throughout the day.

All models in the Desa VGL series are designed with durability in mind, often featuring weather-resistant enclosures suitable for outdoor installations. Additionally, these lights are easy to install and maintain, making them a practical choice for both professional installations and DIY projects.

In summary, the Desa VGL series, encompassing models VGL18NRA, VGL18PRA, VGL24NRA, VGL24PRA, VGL30NRA, and VGL30PRA, stands out for its versatility, energy efficiency, and advanced technology. These lights not only serve diverse lighting needs across various environments but also promise longevity and reduced energy costs, making them an ideal choice for forward-thinking consumers and businesses alike.