Figure 9 - Elbow Offset

VENTING INSTALLATION

Continued

Screws

B

A

Figure 9 - Elbow Offset

FIRESTOP SPACERS (FS-10, 1100EFS-10DM FOR JM36)

Firestop spacers are required at each point where the chimney penetrates a floor space. Their purpose is to establish and maintain the required clearance between the chimney and the combustible materials. When the pipe passes through a framed opening into a living space above, the firestop must be placed onto the ceiling from below as shown in Figure 10.

They also provide complete separation from one floor space to another or attic space as required by most codes. When the double wall pipe passes through a framed opening into an attic space, the firestop must be placed into an attic floor as shown in Figure 11.

 

Existing

 

Ceiling

 

Frame

 

Firestop

 

Spacer

 

Screws or

 

Staples

 

(Min. of 8)

Figure 10 - Firestop Spacer with Living

 

Space Above Ceiling

Firestop

Screws or Staples

(Min. of 8)

Spacer

 

 

Existing

 

Ceiling

 

Frame

Figure 11 - Firestop Spacer with Attic

Space Above Ceiling

PENETRATING THE ROOF

To maintain a 1" (JM36) or 2" (JM42/JM50) clear- ance to the pipe on a roof with a pitch, a rectangular opening must be cut.

1.Determine the center point through which the pipe will penetrate the roof.

2.Determine the center point of the roof. Pitch is the distance the roof drops over a given span, usually 12". A 6/12 pitch means that the roof drops 6" for each 12" one measure horizontally down from the roof rafters.

3.Use the roof opening chart (Figure 12) to determine the correct opening length and flashing required.

 

17" Min.

 

30" Min.

 

(432mm)

1" Min.

 

(762mm)

 

 

 

 

(25mm)

 

 

 

 

1" Min.

 

 

 

(25mm)

 

 

1" Min.

 

 

 

(25mm)

 

 

 

 

Opening "A"

Pitch

Slope

Opening "A"

Used Flashing

 

 

Max.

Model No.

Flat

17"

V6F-10DM

0-

26.6°

19"

V6F-10DM

6/12

 

 

 

6/12-

45.0°

24"

V12F-10DM

12/12

 

 

 

 

Roof Opening JM36

 

19.5" Min.

 

30" Min.

 

(495mm)

2" Min.

(762mm)

 

 

 

 

 

(51mm)

2" Min.

 

 

 

 

 

 

(51mm)

 

 

2" Min.

 

 

 

(51mm)

 

 

 

 

Opening "A"

Pitch

Slope

Opening "A"

Used Flashing

 

 

Max.

Model No.

Flat

19.5"

V6F-10DM

0-

26.6°

22'

V6F-10DM

6/12

 

 

 

6/12-

45.0°

27"

V12F-10DM

12/12

 

 

 

 

Roof Opening JM42/50

Figure 12 - Roof Opening Measurements

10

www.desatech.com

117541-01A

Page 10