Desa (V)JM50 Venting Installation, Continued, USING ELBOW OFFSETS 30E-12DM, Ceiling Support Pipe

Models: (V)JM42

1 24
Download 24 pages 31.17 Kb
Page 9
Image 9
USING ELBOW OFFSETS (30E-12DM)

VENTING INSTALLATION

Continued

USING ELBOW OFFSETS (30E-12DM)

1.To achieve desired offset, you may install combi- nations of 12, 18, 24, 36 and 48" length of double wall pipe (see offset chart and Figure 7).

OFFSET

RISE

 

CHIMNEY LENGTH

 

A

B

48"

36"

24"

18"

12"

4 3/8"

16 3/8"

 

ELBOW SET ONLY

 

9 3/4"

25 1/2"

 

 

 

 

 

 

1

12 3/4"

30 3/4"

 

 

 

 

1

 

 

15"

34 3/4"

 

 

 

1

 

 

 

18"

40"

 

 

 

 

1

 

1

21 1/4"

46 1/4"

 

 

1

 

 

 

 

23 3/4"

49 1/4"

 

 

 

1

1

 

 

27 3/4"

56 3/4"

1

 

 

 

 

 

 

30"

60 3/4"

 

 

1

 

1

 

 

33"

66"

1

 

 

 

 

 

1

36"

71"

1

 

 

 

1

 

 

38 1/4"

75"

 

 

2

 

 

 

 

41 1/4"

80 1/4"

 

 

1

 

1

 

1

45"

86 3/4"

 

 

2

 

 

 

 

46 3/4"

89 1/2"

1

 

 

 

1

 

1

51"

97"

1

 

1

 

 

 

 

53 1/4"

101"

 

 

2

 

1

 

 

56 1/4"

106 1/4"

2

 

 

 

 

 

 

59 1/4"

111 1/2"

1

 

1

 

1

 

 

61 3/4"

115 1/2"

2

 

 

 

 

 

1

64 3/4"

120 3/4"

2

 

 

 

1

 

 

68 1/4"

127"

1

 

2

 

 

 

 

70"

130"

2

 

 

 

1

 

1

74 1/4"

137 1/2"

1

 

2

 

 

 

1

76 3/4"

141 1/2"

1

 

2

 

1

 

 

79 3/4"

146 3/4"

 

 

4

 

 

 

 

OFFSET CHART (22-50 FT. SYSTEM HEIGHT)

2.Chimney weight above offset rests on return elbow. Straps must be securely nailed to rafters or joists (see Figure 8, details a & b).

3.Maximum length of pipe between supports (return elbow or 12S-12DM) is 6' of angle run. Maximum of two 6' angle run sections per chimney system (see Figure 7).

4.All pipe connections between the offset and return must be secured with two screws on the outer pipe only (see Figure 9, page 10). Do not penetrate the inner stainless.

 

 

See Detail A

 

 

2" Min.

Straps

 

 

 

Straps

 

 

Detail B

See Detail B

Angle Firestop

 

Straps

Straps

 

 

 

Detail A

 

Return Elbow

 

Figure 8 - Ceiling Support Pipe

 

12S-12DM

 

Return

Figure 8 - Ceiling Support Pipe Elbow

Offset

Elbow

6' Max.

Return

Elbow

Offset

Elbow

Return Elbow Figure 7 - Typical Offset Terminations

 

Return

 

 

Elbow

 

 

Return

 

 

Elbow

 

6' Max.

Ceiling

 

 

 

 

Support Pipe

 

 

12S-12DM

6' Max.

 

 

6' Max.

Offset

Elbow

A

Offset Elbow

 

Offset

6' Max.

Elbow

 

B

6' Max.

C

Figure 7 - Typical Offset Terminations

117541-01A

www.desatech.com

9

Page 9
Image 9
Desa (V)JM50, (V)JM42, (V)JM36 Venting Installation, Continued, USING ELBOW OFFSETS 30E-12DM, Ceiling Support Pipe