AIR FOR COMBUSTION AND VENTILATION

Continued

Unusually Tight Construction

The air that leaks around doors and win- dows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.

Unusually tight construction is defined as construction where: a.walls and ceilings exposed to

the outside atmosphere have a continuous water vapor re- tarder with a rating of one perm (6x10-11kg per pa-sec-m2) or less with openings gasketed or sealed and

b.weather stripping has been added on openable windows and doors and

c.caulking or sealants are ap- plied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceil- ing joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.

If your home meets all of the three criteria above, you must provide ad- ditional fresh air. See Ventilation Air From Outdoors, page 5.

If your home does not meet all of the three criteria above, proceed to De- termining Fresh-Air Flow For Heater Location.

Confined and Unconfined Space

The National Fuel Gas Code (ANSIZ2123.1, 1992 Section 5.3) defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with

the space in which the appliances are in- stalled*, through openings not furnished with doors, are considered a part of the unconfined space.

*Adjoining rooms are communicating only if there are doorless passageways or ventila- tion grills between them.

DETERMINING AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height =

________ cu. ft. (volume of space)

Example: Space size 18 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2304 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

______ (volume of space) ÷ 50 cu. ft. =

(Maximum Btu/Hr the space can sup- port)

Example: 2304 cu. ft. (volume of space) ÷ 50 cu. ft. = 46.1 or 46,100 (maximum Btu/Hr the space can sup- port)

3.Add the Btu/Hr of all fuel burning ap- pliances in the space.

Vent-free heater __________ Btu/Hr Gas water heater* ________ Btu/Hr

Gas furnace _____________ Btu/Hr Vented gas heater _________ Btu/Hr Gas fireplace logs ________ Btu/Hr

Other gas appliances*+ ____ Btu/Hr

Total

= ___ Btu/Hr

Example:

Gas water heater

40,000 Btu/Hr

Vent-free heater + 10,000 Btu/Hr

Total = 50,000 Btu/Hr

*Do not include direct-vent gas appli- ances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

________ Btu/Hr (maximum the

space can support)

________ Btu/Hr (actual amount of

Btu/Hr used)

 

Example: 46,100

Btu/Hr (maxi-

mum the space can support)

50,000

Btu/Hr (actual

amount of Btu/Hr used)

The space in the above example is a con- fined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventila- tion grills between rooms. See Ventila- tion Air From Inside Building, page 5.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors,page 5.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space, provide ad- equate combustion and ventila- tion air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3 or applicable local codes.

Continued

4

102490

Page 4
Image 4
Desa VN10T Determining AIR Flow for Heater Location, Unusually Tight Construction, Confined and Unconfined Space

VN10T specifications

The Desa VN10T is a sophisticated and versatile piece of machinery designed for various agricultural applications. Known for its robust construction and advanced technology, the VN10T stands out in the market for its efficiency and reliability. This model is particularly favored by farmers looking for a tractor that can handle challenging terrains while providing optimal performance.

One of the standout features of the Desa VN10T is its powerful engine. The tractor is equipped with a high-performance diesel engine that ensures not only substantial horsepower but also excellent torque delivery. This makes it particularly suited for heavy-duty tasks such as plowing, tilling, and hauling materials over uneven surfaces. The engine is designed with fuel efficiency in mind, allowing for longer working hours without the need for frequent refueling.

The VN10T features a user-friendly transmission system, providing smooth shifting and excellent control over various speed ranges. This adaptability allows operators to easily switch between tasks, increasing productivity on the farm. The four-wheel drive option enhances traction and stability, making it ideal for diverse agricultural practices, from planting to harvesting.

Technologically, the Desa VN10T is equipped with an advanced hydraulic system. This system allows for precise control of implements, facilitating a seamless execution of farming tasks. The hydraulic capabilities enable the use of various attachments, such as front loaders, backhoes, and mowers, transforming the tractor into a multipurpose tool on the farm.

Comfort and ease of use are also paramount in the design of the VN10T. The operator's cabin is spacious and ergonomically designed, coming with adjustable seating, intuitive controls, and climate control options. Visibility is enhanced through large windows, ensuring the operator can maneuver the tractor safely and effectively.

In terms of maintenance, the VN10T is designed for ease of access, simplifying routine checks and repairs. This reduces downtime and ensures that farmers can keep their operations running smoothly.

Overall, the Desa VN10T combines power, comfort, and advanced technology, making it an excellent choice for modern agricultural needs. Its ability to adapt to various tasks while maintaining efficiency sets it apart as a reliable partner for farmers.