Venting Installation

instructions

Continued

WARNING: Do not recess vent termination into any wall. This will cause a fire hazard.

6.Noncombustible Exterior Wall: Position the horizontal vent cap in the center of the 7 3/4" round hole and attach to the exterior wall with four wood screws provided. Before attaching the vent cap to exterior wall, run a bead of non-hardening mastic (pliable sealant) around the outside edges to make a seal between it and the outside wall. Note: The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete or other types of sidings.

Combustible Exterior Wall: For vinyl siding, stucco or wood exteriors, a siding standoff may be installed between the vent cap and exterior wall. The siding standoff prevents excessive heat from damaging the siding materials. Siding material must be cut to accommodate standoff. Bolt the vent cap to the standoff. Ap- ply non-hardening mastic around outside edge of standoff. Position the standoff/cap assembly in the center of the 10" square hole and attach to exterior wall with wood screws provided (see Figure 11). The siding standoff must sit flush against the exterior fascia material.

7.Combustible Exterior Wall Only: Slide the wall firestop over the vent pipe before connecting horizontal run to vent cap (see Figure 12).

8.Carefully move fireplace, with vent assembly attached, toward wall and insert vent pipe into horizontal termination. The pipe overlap should be a minimum of 11/4" (see Figure 13, page 11).

9.Combustible Exterior Wall Only: Slide wall firestop against interior wall surface and attach with screws provided. See Figure 13, page 11, for horizontal termination details.

10.Place fireplace into position and shim with noncombustible material if needed. Nail or screw side flanges to framing to secure unit in place. IMPORTANT: Make sure fireplace is level before securing. If fireplace is not level it will not work properly.

Apply Mastic to

All Four Sides

Vent Cap

Wood Screw

Figure 10 - Installing Horizontal Vent Cap

(Noncombustible Exterior)

Cut Siding Away to

Fit Standoff

Standoff Wood

Screw

Vent

Cap

Apply Mastic

Screws

to All Four Sides

 

Figure 11 - Installing Siding Standoff

(Combustible Exterior Wall)

Interior Wall

Surface

Wall

Firestop

Vent Cap (Horizontal Termination)

ScrewHorizontal

Vent Pipe

Figure 12 - Connecting Vent Cap with

Horizontal Vent Pipe

10

www.desatech.com

111251-01E

Page 10
Image 10
Desa (V)T36EPA installation manual Installing Horizontal Vent Cap Noncombustible Exterior