FIREPLACE INSTALLATION

Installing Gas Piping to Fireplace Location (Cont.) Connecting Fireplace to Gas Supply

Checking Gas Connections

FIREPLACE INSTALLATION

Continued

We recommend that you install a sediment trap/drip leg in supply line as shown in Figure 31. Locate sediment trap/drip leg where it is within reach for cleaning. Install in piping system between fuel supply and fireplace. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into fireplace gas con- trols. If sediment trap/drip leg is not installed or is installed wrong, fireplace may not run properly.

CSA Design-Certified

Equipment Shutoff Valve

with 1/8" NPT Tap*

To Gas Supply (Natural)

To External Regulator

(Propane/LP)

Equipment Shutoff Valve

Control Valve

Approved Flexible

Gas Line

3" Minimum

Natural - From Gas Meter (5.5" W.C. to 10.5"

W.C. Pressure)

Propane/LP From External Regulator (11" W.C. to 14" W.C. Pressure)

Flexible Gas Line

Do NOT Kink

Figure 32 - Connecting Flexible Gas Line to Millivolt Valve

CHECKING GAS CONNECTIONS

Cap Pipe Nipple Tee Joint

WARNING: Test all gas piping and connections for leaks after installing or servicing. Correct all leaks

Figure 31 - Gas Connection

Sediment Trap/Drip Leg

at once.

*The CSA design-certified equipment shutoff valve may be sup- plied with the appliance or you can purchase it from your retailer.

CONNECTING FIREPLACE TO GAS SUPPLY

Installation Items Needed

5/16" hex socket wrench or nut-driver

sealant (resistant to propane/LP gas, not provided)

1.Open lower louver door panel by gently pulling forward.

2.Route flexible gas line (provided by installer) from equipment shutoff valve to fireplace. Route flexible gas supply line through one of the access holes on side of fireplace.

3.Attach flexible gas line from gas supply to control valve (see Figure 32).

4.Check all gas connections for leaks. See Checking Gas Connections.

WARNING: Never use an open flame to check for a leak. Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect fireplace and its individual equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig (3.5 kPa) will damage fireplace gas regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fire- place, or using compressed air.

4.Check all joints of gas supply piping system. Apply noncorro- sive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

5.Reconnect fireplace and equipment shutoff valve to gas sup- ply. Check reconnected fittings for leaks.

For..com

108861-01D

Page 20
Image 20
Desa (V)V42P, (V)V42N Checking GAS Connections, Connecting Fireplace to GAS Supply, Installation Items Needed, At once

(V)V42P, CHDV42NR, (V)V36P, (V)V42N, CHDV36NR specifications

Desa (V)V42N, CHDV36NR, (V)V36P, (V)V42P, and CHDV42NR represent a range of cutting-edge technological innovations designed for modern heating solutions. These models exemplify the combination of efficiency, versatility, and advanced control features that cater to diverse user needs in both residential and commercial spaces.

One of the standout features of these models is their energy efficiency. Utilizing the latest in burner technology, they are engineered to provide robust heating with minimal fuel consumption. This not only helps in reducing energy bills but also supports environmentally friendly practices by lowering carbon emissions.

The Desa (V)V42N model is particularly notable for its smart thermostat compatibility. It allows users to integrate their heating system with smart home technologies, enabling remote access and control via mobile applications. This feature ensures users can monitor and adjust their heating settings from anywhere, enhancing convenience and comfort.

In contrast, the CHDV36NR model is designed with a focus on aesthetics and ambiance. This model incorporates a modern design with sleek finishes that can seamlessly blend into various interior styles. Its unique viewing window offers a stunning display of flames, creating a captivating focal point in any room.

For those looking for adaptable heating solutions, the (V)V36P and (V)V42P models are equipped with modular capabilities. These designs allow for easy installation and expansion, accommodating different room sizes and heating needs. Moreover, they feature advanced fan systems that distribute heat evenly, ensuring consistent warmth throughout the space.

The CHDV42NR brings another layer of technology with its dual-fuel capability, allowing users to choose between natural gas and propane. This flexibility is particularly advantageous in regions where fuel availability may vary, ensuring reliable performance regardless of the energy source.

Overall, the Desa (V)V42N, CHDV36NR, (V)V36P, (V)V42P, and CHDV42NR models showcase a robust combination of efficiency, advanced technology, and user-friendly features. Whether enhancing indoor comfort with smart technology, aesthetics, or adaptability, these products set a benchmark in the heating solution market. They are perfect for those seeking reliable performance and modern design in their heating systems.