troubleshooting

Continued

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

 

 

 

 

When ignitor button is pressed,

1. Gas supply turned off or

1.

Turn on gas supply or open

there is spark at pilot but no

 

equipment shutoff valve

 

equipment shutoff valve

ignition (GA9050A-1 Only)

 

closed

 

 

 

2.

Control knob not in PILOT

2.

Turn control knob to PILOT

 

 

position

 

position

 

3.

Control knob not pressed

3.

Press in control knob while

 

 

in while in PILOT position

 

in PILOT position

 

4.

Air in gas lines when in-

4.

Continue holding down

 

 

stalled

 

control knob. Repeat ignit-

 

 

 

 

ing operation until air is

 

 

 

 

removed

 

5.

Pilot adjustment screw

5.

Adjust pilot flame for ap-

 

 

closed

 

proximately 2" blue flame

 

6.

Pilot is clogged

6.

Clean pilot (see Cleaning

 

 

 

 

and Maintenance, page 15)

 

 

 

 

or replace pilot assembly

 

7.

Low gas pressure

7.

Replace gas control

 

 

 

 

Pilot lights but flame goes out

1. Control knob not fully

1.

Press in control knob fully

when control knob is released

 

pressed in

 

 

(GA9050A-1 Only)

2. Control knob not pressed

2.

After pilot lights, keep con-

 

 

in long enough

 

trol knob pressed in 30

 

 

 

 

seconds

 

3.

Equipment shutoff valve

3.

Fully open equipment shut-

 

 

not fully open

 

off valve

 

4.

Pilot flame not touching

4.

A) Contact local natural gas

 

 

thermocouple, which al-

 

company

 

 

lows thermocouple to cool,

 

 

 

 

causing pilot flame to go

 

B) Clean pilot (see Cleaning

 

 

out. This problem could

 

and Maintenance, page 15)

 

 

be caused by one or both

 

or replace pilot assembly

 

 

of the following:

 

 

 

 

A) Low gas pressure

 

 

 

 

B) Dirty or partially clogged

 

 

 

 

pilot

 

 

 

5.

Thermocouple connection

5.

Hand tighten until snug,

 

 

loose at control valve

 

then tighten 1/4 turn more

 

6.

Thermocouple damaged

6.

Replace thermocouple

 

7.

Control valve damaged

7.

Replace control valve

 

 

 

 

Burner does not light after pilot

1. Burner orifice clogged

1.

Clean burner orifice

is lit (GA9050A-1 Only)

2. Inlet gas pressure is too

2.

Contact local natural or

 

 

low

 

propane/LP gas company

 

3.

Thermocouple leads dis-

3.

Reconnect leads

 

 

connected or improperly

 

 

 

 

connected

 

 

 

 

 

 

Delayed ignition burner

1. Pilot flame needs adjusting

1.

Adjust pilot flame for ap-

(GA9050A-1 Only)

 

 

 

proximately 2" blue flame

 

2.

Wrong pilot orifice

2.

Replace pilot orifice set

124183-01B