
Installation
Continued
CAUTION: Combustion air inlet ducts shall not terminate in attic space.
The maximum height for the air vent can not exceed 3 feet below the flue gas outlet of the termination.
Secure to Collars with Metal Tape, Screws or Straps (Min. of 1/4" x 20" in size)
| Air Inlet |
| Location |
| Must Allow |
| For Bushes |
| or Snow |
| Air Inlet |
| Eyebrow |
Vented Crawl Space | Vent Hood |
(Check Local Codes | Required for |
Before Installing in a | Wall Installation |
Vented Crawl Space)
Figure 5 - Outside Air Kit
Chimney Pipe
DESA Heating, LLC chimney system consists of 12", 18", 24", 36"' and 48"
LINEAL GAIN
PART NO. | DESCRIPTION | GAIN (IN) | |
48" Plantation | Fireplace | 66 1/2" | |
Pipe Section | 10 5/8" | ||
Pipe Section | 16 5/8" | ||
|
| ||
Pipe Section | 23 5/8" | ||
|
| ||
Pipe Section | 34 5/8" | ||
Pipe Section | 46 5/8" | ||
|
| ||
Round | 7 3/4"* | ||
Termination | |||
| |||
| Square Chase- |
| |
Top with Slip | 7" to 15"* | ||
| Section |
|
*The lineal gain for the terminations is mea- sured to the flue gas outlet height.
15" Galvanized
Outer Pipe
12 3/8" | Hemmed |
Stainless | End |
| |
Inner Pipe |
|
Figure 6 - Lineal Gain
Assembly and installation of double wall chimney system
Each double wall chimney section consists of a galvanized outer pipe, a stainless steel inner flue pipe and a wire spacer. Pipe sections must be assembled independently as chimney is installed. When connecting chimney directly to fireplace, inner flue pipe section must be installed first with lanced side up. Outer pipe section can then be installed over flue pipe section with hemmed end up. Press down on each pipe section until lances securely engage hem on fireplace starter. Wire will assure proper spacing between inner and
WARNING: The opening in the collar around the chimney at the top of the fireplace must not be obstructed.Neveruseblowninsulation to fill the chimney enclosure.
outer pipe sections.
Continue to assemble chimney sections as outlined above, making sure both inner and outer pipe sections are locked together. When installing double wall
6 | www.desatech.com |