Installation

Continued

CAUTION: Combustion air inlet ducts shall not terminate in attic space.

The maximum height for the air vent can not exceed 3 feet below the flue gas outlet of the termination.

Secure to Collars with Metal Tape, Screws or Straps (Min. of 1/4" x 20" in size)

 

Air Inlet

 

Location

 

Must Allow

 

For Bushes

 

or Snow

 

Air Inlet

 

Eyebrow

Vented Crawl Space

Vent Hood

(Check Local Codes

Required for

Before Installing in a

Wall Installation

Vented Crawl Space)

Figure 5 - Outside Air Kit

Chimney Pipe

DESA Heating, LLC chimney system consists of 12", 18", 24", 36"' and 48" snap-lock, double- wall pipe segments, planned for maximum adaptability to individual site requirements. Actual lengths gained after fitting overlaps must be taken into consideration (lineal gain) and are given in lineal gain chart (see Figure 6). Lineal gain is the actual measurable length of a part after two or more parts are connected. For Canada, use chimney parts designated "HT".

LINEAL GAIN

PART NO.

DESCRIPTION

GAIN (IN)

48" Plantation

Fireplace

66 1/2"

12-12DM

Pipe Section

10 5/8"

12-12HT

18-12DM

Pipe Section

16 5/8"

18-12HT

 

 

24-12DM

Pipe Section

23 5/8"

24-12HT

 

 

36-12DM

Pipe Section

34 5/8"

36-12HT

48-12DM

Pipe Section

46 5/8"

48-12HT

 

 

RLT-12D

Round

7 3/4"*

RLT-12HT

Termination

 

 

Square Chase-

 

STL-12D

Top with Slip

7" to 15"*

 

Section

 

*The lineal gain for the terminations is mea- sured to the flue gas outlet height.

15" Galvanized

Outer Pipe

12 3/8"

Hemmed

Stainless

End

 

Inner Pipe

 

Figure 6 - Lineal Gain

Assembly and installation of double wall chimney system

Each double wall chimney section consists of a galvanized outer pipe, a stainless steel inner flue pipe and a wire spacer. Pipe sections must be assembled independently as chimney is installed. When connecting chimney directly to fireplace, inner flue pipe section must be installed first with lanced side up. Outer pipe section can then be installed over flue pipe section with hemmed end up. Press down on each pipe section until lances securely engage hem on fireplace starter. Wire will assure proper spacing between inner and

WARNING: The opening in the collar around the chimney at the top of the fireplace must not be obstructed.Neveruseblowninsulation to fill the chimney enclosure.

outer pipe sections.

Continue to assemble chimney sections as outlined above, making sure both inner and outer pipe sections are locked together. When installing double wall snap-lock chimney to- gether, it is important to assure joint between chimney sections is locked. Check by pulling chimney upward after locking. Chimney will not come apart if properly locked. It is not necessary to add screws to keep chimney together (exception, see Figure 9, page 8).

6

www.desatech.com

122272-01C