Installation

Continued

Flashing installation (v6f-10dm

Terminations/Spark Arrestor

or v12f-10dm)

 

Fireplace system must be terminated with

Determine flashing to be used with roof open-

listed round top or chase terminations. In any

case, refer to installation instructions supplied

ing chart. Slide flashing over pipe until base is

with termination.

 

flat against roof. Replace as many shingles as

 

 

 

needed to cover exposed area and flashing

CAUTION: Do not seal open-

base. Secure in position by nailing through

ings on the rooftop flashing.

shingles (see Figure 13). DO NOT NAIL

THROUGH FLASHING CONE.

Follow installation instructions

Storm

 

provided with termination being

Overlap

used.

 

Collar

 

Shingles Top

 

 

Flashing

 

 

and Sides Only

 

 

Cone

 

 

 

 

RLT-12D

Nail Only

 

 

 

Stainless

(Shown)

Outer

 

 

Inner Flue

 

Perimeter

 

 

 

Pipe

Level of

of Flashing

 

 

 

Flue Gas

 

 

 

 

 

Secure

Outlet

 

 

 

 

 

Termination

 

 

 

to Outer

Waterproof

 

 

Pipe with 3

 

 

Caulking

 

 

Screws

 

 

Storm

Underlap

 

 

Shingles

 

 

Collar

at Bottom

Flashing

 

Figure 13 - Flashing Installation

Installing Flashing on a Metal Roof When installing the flashing on a metal roof, it is required that putty tape be used between the flashing and the roof. The flashing must be secured to the roof using #8 x 3/4" screws and then sealed with roof coating to prevent leakage through the screw holes. A roof coating must also be applied around the perimeter of the flashing to provide a proper seal.

Storm Collar Installation (SC2-1)

Place storm collar over pipe and slide down until it is snug against open edge of flashing (see Figure 14). Apply waterproof caulk around perimeter of collar to provide a proper seal.

Chimney

Waterproof

Pipe

Caulk

Storm

Flashing

Collar

Overlap

 

Shingles (Top

Underlap

and Sides of

Shingles

Flashing Base)

 

Figure 15 - Termination

Chase installations

Instructions for chase installations are included with the chase style termination chosen. In a multiple chase installation, be sure to provide adequate distance between terminations to prevent smoke spillage from one termination to another. Terminations must be separated a minimum of 24" center to center and stacked at a minimum vertical height difference of 18" (see Figure 16, page 10).

Note: If a decorative shroud is to be installed, contact the manufacturer for specifications.

Figure 14 - Storm Collar

122272-01C

www.desatech.com