Installation
Continued
| Penetrating roof |
| ||
| To maintain a 2" clearance to pipe on roof with | |||
| a pitch, a rectangular opening must be cut. | |||
Screws | 1. | Determine center point through which pipe | ||
| will penetrate roof. |
| ||
B |
|
| ||
2. Determine center point of roof. Pitch is | ||||
| ||||
|
| the distance the roof drops over a given | ||
|
| span, usually 12". |
| |
| 3. Use roof opening chart (Figure 12) to | |||
|
| determine correct opening length and | ||
|
| flashing required. |
| |
A | 4. Remove shingles around opening mea- | |||
Figure 9 - Elbow Offset |
| sured. Cut out this section. |
| |
Firestop Spacers | 5. | Add next sections of pipe until end | ||
Firestop spacers are required at each point |
| penetrates roof line. Check to see that | ||
where chimney penetrates a floor space. |
| proper clearances are maintained. Extend | ||
Their purpose is to establish and maintain |
| chimney by adding sections of double wall | ||
required clearance between chimney and |
| pipe until pipe is minimum of 30" above | ||
combustible materials. When pipe passes |
| highest point of roof cutout. Termination | ||
through a framed opening into a living space |
| and chimney must extend a minimum of | ||
above, firestop must be placed onto ceiling |
| 36" above highest point where it passes | ||
from below as shown in Figure 10. |
| through roof. |
| |
They also provide complete separation from |
|
|
| |
one floor space to another or attic space as |
|
|
| |
required by most codes. When the double wall |
| 19.5" Min. | 30" Min. | |
pipe passes through a framed opening into an |
| 2" Min. |
| |
attic space, the firestop must be placed into |
|
| 2" Min. | |
an attic floor as shown in Figure 11. |
|
|
| |
Existing |
| 2" Min. |
| |
Ceiling |
|
| ||
|
|
| ||
Frame |
|
|
|
Firestop | Opening "A" | |
Spacer | ||
|
| Screws or | Pitch | Slope | Opening | Used Flashing | |
| Staples | |||||
| (Min. of 8) |
|
| "A" Max. | Model No. | |
| Flat | 0° | 19.5" | |||
Figure 10 - Firestop Spacer with Living | ||||||
26.6° | 22' | |||||
| Space Above Ceiling | |||||
| 45.0° | 27" | ||||
|
| |||||
Firestop | Screws or Staples | Figure 12 - Roof Opening Measurements | ||||
(Min. of 8) |
|
|
|
| ||
Spacer |
|
|
|
|
| |
| Existing |
|
|
|
| |
| Ceiling |
|
|
|
| |
| Frame |
|
|
|
| |
Figure 11 - Firestop Spacer with Attic |
|
|
|
| ||
| Space Above Ceiling |
|
|
|
|
8 | www.desatech.com |