Desa Tech CGN30TL, CGN20TL Connecting To Gas Supply, Typical Inlet Pipe Diameters

Models: CGN20T CGN30TL CGN30T CGN20TL

1 32
Download 32 pages 39.83 Kb
Page 14
Image 14
CONNECTING TO GAS SUPPLY

CONNECTING TO GAS SUPPLY

NOTICE

A qualified service person must connect heater to gas supply. Fol- low all local codes.

WARNING

WARNING ICON

G 001

Never connect heater to private (non-utility) gas wells. This gas is commonly known as well-head gas.

IMPORTANT: Check gas line pressure before connecting heater to gas line. Gas line pressure must be no greater than 14 inches of water. If gas line pressure is higher, heater regulator damage could occur.

CAUTION

WARNING ICON

G 001

Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of large enough diameter to allow proper gas volume to heater. If pipe is too small, undue loss of pressure will occur.

Typical Inlet Pipe Diameters

20,000

Btu/Hr Models

3/8" or greater

30,000

Btu/Hr Model

1/2" or greater

Installation must include a manual shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 13, page 15).

Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.

CAUTION

WARNING ICON

G 001

Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

Install sediment trap in supply line as shown in Figure 13, page 15. Locate sediment trap where it is within reach for cleaning. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.

14

103873

Page 14
Image 14
Desa Tech CGN30TL, CGN20TL installation manual Connecting To Gas Supply, Typical Inlet Pipe Diameters