FRESH AIR

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

FOR

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

COMBUSTION

Space: Includes the room in which you will install heater plus any adjoining rooms

AND

with doorless passageways or ventilation grills between the rooms.

VENTILATION

1. Determine the volume of the space (length x width x height).

 

Continued

Length x Width x Height = _________________

cu. ft. (volume of space)

Example:

Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) =

 

 

 

2560 cu. ft. (volume of space)

 

 

 

If additional ventilation to adjoining room is supplied with grills or openings, add

 

the volume of these rooms to the total volume of the space.

 

2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the

 

space can support.

 

 

 

 

 

___________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can

 

support)

 

 

 

 

 

 

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum

 

Btu/Hr the space can support)

 

 

 

 

 

3. Add the Btu/Hr of all fuel burning appliances in the space.

 

 

Vent-free heater

 

_________________ Btu/Hr

 

 

Gas water heater*

 

_________________ Btu/Hr

 

 

Gas furnace

 

_________________ Btu/Hr

 

 

Vented gas heater

 

_________________ Btu/Hr

 

 

Gas fireplace logs

 

_________________ Btu/Hr

 

 

Other gas appliances*

+ _________________ Btu/Hr

 

 

Total

= _________________ Btu/Hr

 

Example:

Gas water heater

 

40,000

 

Btu/Hr

 

 

Vent-free heater

+

20,000

 

Btu/Hr

 

 

Total

=

60,000

 

Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_______________

Btu/Hr (maximum the space can support)

_______________

Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200

Btu/Hr (maximum the space can support)

60,000

Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 8.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

6

103873