OWNER’S MANUAL

AIR FOR

COMBUSTION AND

VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = ____________________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) ÷ 50 cu. ft. = (maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

___________________ Btu/Hr

 

 

 

 

Gas water heater*

___________________ Btu/Hr

Example:

 

 

 

Gas furnace

___________________ Btu/Hr

 

 

 

Gas water heater

 

40,000

Btu/Hr

Vented gas heater

___________________ Btu/Hr

 

Vent-free heater

+

30,000

Btu/Hr

Gas fireplace logs

___________________ Btu/Hr

 

 

 

 

Total

=

70,000

Btu/Hr

Other gas appliances* + ___________________ Btu/Hr

 

 

 

 

Total

= ___________________ Btu/Hr

 

 

 

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 70,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.

Continued

104464

5

Page 5
Image 5
Desa Tech SL30PT installation manual AIR for Combustion Ventilation, Determining FRESH-AIR Flow for Heater Location

SL30PT specifications

Desa Tech SL30PT is a cutting-edge product that combines durability, efficiency, and advanced technology to meet the needs of modern consumers. This innovative device is designed for versatility, making it an ideal choice for a wide range of applications, including industrial, commercial, and residential use.

One of the standout features of the SL30PT is its robust construction. Built with high-quality materials, the device is engineered to withstand demanding environments, ensuring longevity and reliability. Its rugged design makes it resistant to impacts, moisture, and varying temperatures, allowing users to deploy it in diverse settings without worrying about performance degradation.

The SL30PT incorporates advanced technology to enhance its functionality. It features an intuitive user interface that simplifies operation, making it accessible for both seasoned professionals and those new to the technology. The device offers seamless connectivity options, including Wi-Fi and Bluetooth, enabling users to integrate it easily with other smart devices and systems. This connectivity allows for remote monitoring and control, further enhancing its utility in various environments.

Another key characteristic of the SL30PT is its energy efficiency. The device has been designed to minimize energy consumption while maintaining optimal performance, making it an environmentally friendly choice. This focus on sustainability not only reduces operating costs for users but also aligns with the growing demand for eco-conscious products.

Performance-wise, the SL30PT boasts impressive power and speed, ensuring that it can handle a wide range of tasks efficiently. The device is equipped with advanced processing capabilities that enable it to execute complex functions quickly, thereby improving productivity. Additionally, the SL30PT is compatible with various accessories and attachments, which can further expand its functionality and cater to specific user needs.

Furthermore, the device is backed by a comprehensive support system, including detailed user manuals and responsive customer service. This commitment to customer satisfaction ensures that users can maximize the benefits of the SL30PT while receiving assistance whenever needed.

In summary, Desa Tech SL30PT stands out as a versatile, durable, and technologically advanced device. Its robust construction, energy efficiency, and advanced connectivity options make it suitable for various applications, making it a valuable investment for users seeking reliable and innovative solutions.