6.2
5 Installation
5.1General Information
The unit must be installed indoors on a level, smooth and hori- zontal surface. The entire base of the frame should lie directly on the floor to ensure a good soundproof seal. If this is not the case, additional sound insulation measures may be necessary. If the device is installed on top of a
P
P | P |
P
Never install the device in rooms subject to high humidity. Con- densation can form on the heat pump and air circuit if the humid- ity exceeds 50 % and the external temperature is below
O °C.
If the heat pump is installed on an upper storey, the
5.2Condensed Water Pipe
Condensed water that forms during operation must be drained off frost free. The heat pump must be mounted on a level plane to guarantee proper drainage. The condensed water pipe must have a minimum diameter of 50 mm and should be fed
5.3Sound
To prevent
Installed air ducts should be
6 Installation
6.1General Information
The following connections need to be established on the heat pump:
Fresh and exhaust air
Flow and return flow of the heating system
Condensate outflow
Control line to the heat pump controller
Power supply
6.2Air Connection
ATTENTION!
Do not restrict or block up the area around the air inlet or outlet.
ATTENTION!
Only operate the heat pump with the air ducts connected.
The glass fibre reinforced concrete air ducts offered as accesso- ries are
The sealing collar is used to seal the air ducts on the heat pump. The air ducts are not screwed directly onto the heat pump. Only the rubber seal comes into direct contact with the heat pump when the system is installed correctly. This guarantees easy as- sembly and disassembly of the heat pump and also ensures that
If another type of air duct is used, observe the external and inter- nal dimensions as specified in the figure. Also ensure that the vi- bration and duct insulation are adequate.
If
English
www.dimplex.de |