620515, 620525, 620526, 630515 & 630516 Installation Instructions

4. Air Distribution System Sizing & Design

CAUTION

It is the responsibility of the installer to insure the ductwork will not collapse or bend during and after the installation. Dometic Corporation will not be liable for roof structural or ceiling damage due to improperly insulated, sealed or collapsed ductwork.

The Installer of this air conditioner system must design the air distribution system for their particular application. Several requirements for this system MUST be met for the air conditioner to operate properly. These requirements are as follows:

a.The duct material must meet or exceed any agency or RVIA Standard that may be in exist- ence at the time the RV is produced.

b.All discharge air ducts must be properly insu- lated to prevent condensation from forming on their surfaces or adjacent surfaces during op- eration of the air conditioner. This insulation must be R-7 minimum.

c.Ducts and their joints must be sealed to prevent condensation from forming on adjacent sur- faces during operation of the air conditioner.

d.Returnairopeningsmusthave40squareinches minimum free area including the filter.

e.Return air to the air conditioner must be filtered to prevent dirt accumulation on air conditioner cooling surface.

5.Air Distribution System Installation

a.Dometic Corporation recommends the basic configuration shown on page 7, for installing this air conditioner system. We have found by testing, that this configuration works best in most applications of this air conditioner sys- tem. It is the responsibility of the Installer of this system to review each RV floor plan and deter- mine the following:

Duct size

Duct layout

Register size

Register location

Thermostat location

AIR DISTRIBUTION

DUCT SIZING & DESIGN CHART

Return Air Cover Model

3105007

3308120

 

3105935

Genesis Air Filtration System

 

 

 

Roof Cavity Depth

2.0 In. Min. - 5-1/2 In. Max.

2.0 In. Min. - 5-1/2 In. Max.

 

 

 

Duct Cross Sectional Area

21.0 Sq. In. Min.

32.0 Sq. In. Min.

 

 

 

Duct Size

 

 

Depth

1-1/2 In. Min. - 2-1/2 In. Max.

2.0 In. Min. - 2-1/2 In. Max.

Width

7.0 In. Min. - 10.0 In. Max.

8.0 In. Min. - 10.0 In. Max.

Total Duct Length

15.0 Ft. Min. - 40.0 Ft. Max.

15.0 Ft. Min. - 40.0 Ft. Max.

Duct Length (short run)

1/3 Total Duct Length

1/3 Total Duct Length

 

 

 

Center Duct System (Only)

 

 

Depth

 

2.0" In. Min. - 2.0" Max.

Width

 

8.0 In. Min. - 8.0 In. Max.

Total Duct Length

 

15.0 Ft Min. - 40 Ft. Max.

Duct Length (Short Run)

 

1/3 Total Length

 

 

 

Register Requirements

 

 

Number Required Per Run

4 Min.

4 Min.

Register Free Air Area

14.0 Sq. In.

14.0 Sq. In.

Distance From Duct End

5.0 In. Min. - 8.0 In. Max.

5.0 In. Min. - 8.0 In. Max.

Distance From Elbow

15.0 In.

15.0 In.

 

 

 

Duct Static

 

 

Blower at High Speed,

 

 

Filter & Grill In Place

0.12 - 0.65 In. W.C.

0.12 - 0.65 In. W.C.

 

 

 

Note: Duct sizes listed are inside dimensions.