Freightliner Refrigerator Troubleshooting Guide
750000005 (TJ18F)
750000011 (TJ22F)
750000026 (TJ18FP3)
Specific Trouble-Shooting of
Electrical Components
A:Check incoming voltage
1.Hold multimeter leads to the positive (+) and negative
2.The inrush current must not drop the voltage more than 3% or .36 volts when the compressor is initially energized. Monitor this voltage by using a multimeter at
3.Verify that voltage at unit is equal to voltage at source. If the voltage is less than at the source then the wire used from source to unit is too small.
B. Checking the Compressor
1.Remove all wires from compressor module (make note where they are connected).
2.Removed Danfoss module from the compressor by removing the mounting screw and twisting the module to the rear to disconnect it from the compressor. See
Section A #12 in “General Troubleshooting” Section.
3.Compressor windings can be checked for defects by measuring the resistance on the current