Dometic Elite RM7732 manual Testing Lpgassafetyshutoff, 10. 120 VOLT AC ELECTRICAL CONNECTION

Models: Elite RM7732

1 14
Download 14 pages 59.97 Kb
Page 6
Image 6
9. TESTING LPGASSAFETYSHUTOFF

The gas supply system must incorporate a pressure regulator to maintain a supply pressure of not more than 13-1/2 inches water column, (static) no load.

To test the gas safety shutoff, proceed as follows: PRESSURE

LP GASREGULATOR

CYLINDER

TO

REFRIGERATOR

When testing the gas supply system at pressures less than or equal to 1/2 psig, the appliance must be isolated from the gas supply piping by closing its individual manual shutoff valve.

In case detailed instructions on the installation and con- nection to the gas supply are required, contact your dealer or distributor.

E.Remove cover (see FIG. 12) and open the manual gas valve. Apply a noncorrosive commercial bubble solution to burner jet (see FIG. 12).

DO NOT USE A FLAME

TO CHECK FOR GAS LEAKS.

F.No bubbles should appear at the opening of the burner jet. The presence of bubbles indicates a defective gas safety shutoff, and service is required.

G.If no bubbles were present at the burner jet, the gas safety valve is working properly. Rinse jet thoroughly with fresh water before proceeding. Be careful not to damage burner jet. Replace cover and turn the main switch OFF and back ON. (See "Section C. Operation Instructions, Item 2. Control Panel"). Normal operation of the burner should return. Allow the burner to operate for a minimum of 5 minutes.

9. TESTING LPGASSAFETYSHUTOFF

The gas safety shutoff must be tested after the refrigerator is connected to LP gas supply.

To test the gas safety shutoff, proceed as follows:

A.Start the refrigerator according to the instructions, and switch to gas mode. See "Section C. Operation Instruc- tions."

B.Check that the gas flame is lit and the gas mode indicator lamp (C) is on. See FIG. 15.

C.Close the manual shutoff valve at the back of the refrigerator. (See FIG. 12)

D.Wait for one minute. The check indicator lamp (D) should now be lit and the gas mode indicator lamp should be off.

10. 120 VOLT AC ELECTRICAL CONNECTION

The refrigerator is equipped with a three-prong (grounded) plug for protection against shock hazards, and should be plugged directly into a properly grounded three-prong receptacle.

DO NOT cut or remove the grounding prong from this plug.

The power cord should be routed to avoid direct contact with the burner cover, flue cover or manual gas shutoff valve knob. The free length of the cord is 2 feet and therefore recommended that the receptacle be located to the right side of the refrigerator (viewed from the rear) and approximately 10 inches from the floor (see FIG. 13).

FIG. 12

FIG. 13

 

6

Page 6
Image 6
Dometic Elite RM7732 manual Testing Lpgassafetyshutoff, 10. 120 VOLT AC ELECTRICAL CONNECTION