![Using Accessory Lift Kit](/images/new-backgrounds/33982/339825x1.webp)
Using Accessory Lift Kit | |
| Lifting Bracket |
Spreaders | Accessory |
(Field Supplied) | Sheet Metal |
| |
| Screw |
| To avoid possible |
| damage to unit |
| panels from lifting |
| clevis, place |
| packing material |
| between clevis |
| and panels before |
| lifting unit. |
Figure 1
Roof Curb Installation
If a roof curb is used, follow the manufacturer’s Installation Instructions and be sure that all required clearances are observed (see following Clearances section).
Roof Curb Assembly
Minimum Clearance Requirements
| To | For | For | |
| Combustible | Proper | ||
| Service | |||
| Material | Operation | ||
|
| |||
|
|
|
| |
Front | 0" | 48" | 3" | |
|
|
|
| |
Rear | 0" | 24" | 3" | |
|
|
|
| |
Condenser | 0" | 24" | 3" | |
End | ||||
|
|
| ||
|
|
|
| |
Blower | 0" | 30" | 0" | |
End | ||||
|
|
| ||
|
|
|
| |
Top | 0" | 36" | 36" | |
|
|
|
|
Table 1
Condensate Drain
The SH package unit is equipped with a 3/4" FPT cou- pling for condensate line connection. Plumbing must conform to local codes. Use a sealing compound on male pipe threads.
The condensate drain line must be properly trapped and routed to a suitable drain. See Figure 3 for proper
drain arrangement.The drain line must pitch to an open drain or pump to prevent clogging of the line. Seal around the drain connection with suitable material to prevent air leakage into the return air system.
Figure 2
Clearances
All units require certain clearances for proper operation and service. Refer to Table 1 for the minimum clearances to combustibles as well as minimum clearances necessary for servicing and proper unit operation.
Typical Condensate Drain Connection
Unit | Drain Connection |
1.00" Min.
In the U.S., units may be installed on combustible floors made from wood or class A, B, or C roof covering material. In Canada, units may be installed on combustible floors.
12.00"
Max.
3.00" Min.
Service Access
Access to all serviceable components is provided by four removable panels: filter compartment, blower compart- ment, heater compartment, and top panel.
# 48369K005
Positive Liquid Seal Required
Figure 3
Page 3