Eaton Electrical 1000 LCD Programming Procedure, Login, Set Date/Time/DST/Location, Group A GRPA

Models: 1000

1 8
Download 8 pages 44.77 Kb
Page 2
Image 2
LCD Programming Procedure

LCD Programming Procedure

1. Press any key to begin. The Eaton logo will be displayed:

After a few seconds, the firmware version will be displayed:

FIRMWARE VERSION A1

After a few more seconds, the initial status screen will be displayed:

Aug 25, 2006 11:28A

Group Status:

ON: ABC

N

OFF: DEFGHIJKLM OP

Press SEL for menu

Press SEL to get to the MAIN MENU.

2. Login

If user passwords have been created on your system by your distrib- utor/installer, you will see the following screen. Use UP/DOWN to enter the letters of your password and the SEL key to advance to the next letter. Advance the cursor past the end of the blanks to submit the password.

Aug 25, 2006 11:28A

User ID:

________

If this LCD tool has just been powered up, it will have to download a database from the PRC1000 controller. You may see the following screen with the progress indicator:

Aug 25, 2006 11:28A

Refreshing Database

Please wait... 57%

Press BACK to quit

The database may take up to 10 minutes to download during initial startup. Afterwards, the MAIN MENU will be displayed:

MAIN MENU

 

Command

Groups ON/OFF

 

Panel Status Screen

 

Configure Groups

 

Configure Date/Time

_

Group

Status:

 

ON: ABC

N

 

OFF:

DEFGHIJKLM OP

 

3. Set Date/Time/DST/Location

From the MAIN MENU, select Configure Date/Time. The follow- ing menu will be displayed:

CONFIGURE DATE/TIME

Change Date__08/23/06

Change Time 11:37 AM

Change DST MANUAL

St: mm/dd End: mm/dd

Change Astro Loc.

Use UP/DOWN to select Change Date. Use SEL to move through the date digits. Use UP/DOWN to set the month, day and year, respec- tively. After setting the year, hit SEL one more time. The new values will be displayed on the PRC1000.

Use UP/DOWN to highlight Change Time. Use SEL to move through the time digits. Use UP/DOWN to set the hour, minute and AM/PM, respectively. After setting the AM/PM, hit SEL one more time.

The new values will be displayed on the PRC1000.

Use UP/DOWN to highlight Change DST. Use SEL to start editing the DST setting. Use UP/DOWN to choose NONE, AUTO or MANUAL. If MANUAL is chosen, settings for start and end date will appear. Hit SEL to jump to the start date. Use UP/DOWN to set the month and day values. Use SEL to move through the digits. After setting the DST setting (or dates for MANUAL), hit SEL one more time. The new values will be displayed on the PRC1000.

Use UP/DOWN to highlight Change ASTRO-Loc. Hit SEL to start editing the location. The following screen will be displayed:

ASTRO LAT: 33.00

LON: 84.00

TIMEZONE: 5

RISE 06:30 SET 07:00

Use UP/DOWN to set the latitude value in degrees. The latitude range is -90 (South) to +90 (North).

Note: Sunrise/sunset calculations lose accuracy outside the -62 to +62 range. Hit SEL to move to the longitude setting. Use UP/DOWN to set the longitude value in degrees. The longitude range is +180 (Alaska) to -180 (Western Pacific). Hit SEL to move to the timezone setting. Use UP/DOWN to set the timezone value in hours. The timezone range is +12 hours (west of GMT) to -12 hours (east of GMT). After setting the timezone, hit SEL one more time. The new values will be displayed on the PRC1000. The RISE and SET times will update with the new values calculated from the input latitude and longitude and the screen will return to the Configure Date/Time menu. Use BACK to return to the MAIN MENU.

4. Configure Breaker Group A

From the MAIN MENU, select Configure Groups. The following screen will be displayed:

SELECT GROUP

TO CONFIGURE:

Group A GRPA

OFF

GROUP A LIGHTS

15 loads in group.

Use up/down/sel to change selection

The group is shown, followed by its current status (OFF in this example). The next line is the group description, if it exists (GROUP A LIGHTS in this example), followed by the number of loads (breakers) that has been associated with this group (15 in this example).

2

EATON CORPORATION Cutler-HammerPow-R-Command 1000 LCD Display Instruction Leaflet IL01412010E Effective: June 2006

Page 2
Image 2
Eaton Electrical 1000 LCD Programming Procedure, Press any key to begin. The Eaton logo will be displayed, Login