I.B. 29C892B

 

 

Page 9

Table 2.1 Programmable Categories

 

 

 

 

 

 

 

Displayed

 

Display

 

Additional Comments

Menu Items

 

Definition

 

 

 

 

 

 

 

SA

SELECT ADDRESS

Network use only – permits selection of specific trip unit address within network

 

 

 

FI

FIND BAUD/ADDR

Search to identify address and baud rate of connected trip unit (8 conductor custom phone cord only)

 

 

 

ID

FIND PRODUCT ID

Identification of type and frame rating of connected breaker

 

 

 

BA

CHANGE BAUD/ADDRESS

Permits the initial setup or changing of address and baud rate of connected trip unit –

 

 

 

valid password required to setup or change address

 

 

 

RP

RATING PLUG

Rating plug size installed in connected trip unit

 

 

 

ME

METERED VALUES

Depending on trip unit connected, some or all of the values are displayed:

 

Current (A)

- Phases A, B, C, Ground and Neutral

 

Energy (kWh)

- Total, Forward and Reverse

 

Power (kW)

- Power and Peak Demand

 

Power Factor

 

 

 

THD Currents (%)

- Phases A, B, C and Neutral

 

Harmonic Content

- Phases A, B, C and Neutral

 

 

 

TM

TEST MODE

Provides for Phase or Ground, Trip or Non-Trip Test (valid password)

 

 

 

SP

SETPOINTS

Permits viewing, initial setup and changing of setpoints for connected trip unit – valid password

 

 

 

required to setup or change setpoints:

 

LD

-

Long Delay Setting

 

LDTI

-

Long Delay Time

 

LDA

-

Long Delay Action

 

LDS

-

Long Delay Slope

 

SDPU

-

Short Delay Setting

 

SDTI

-

Short Delay Time

 

SDA

-

Short Delay Action

 

SDS

-

Short Delay Slope

 

IN

-

Instantaneous Setting

 

INA

-

Instantaneous Action

 

DSC

-

Discriminator

 

GFP

-

Ground Fault Setting

 

GFT

-

Ground Fault Time

 

GFA

-

Ground Fault Action

 

GFS

-

Ground Fault Slope

 

HLA

-

High Load Setting

 

PTM

-

Powered Thermal Memory

 

UPM

-

Unpowered Thermal Memory

 

FRQ

-

Line Frequency

 

NR

-

Neutral Ratio

 

AWC

-

Auto Waveform Capture

 

PI

-

Phase A Identification

 

 

 

PA

PASSWORD

Permits authorized personnel to change or enter 4 digit password

 

 

 

TC

TRIP EVENT COUNT

Display of number of circuit breaker automatic trip operations

 

 

 

CT

CAUSE-OF-TRIP

Displays one of four possible modes of trip on most recent automatic trip operation:

 

 

 

Long Delay

 

 

 

Short Delay

 

 

 

Instantaneous

 

 

 

Ground Fault

 

 

 

FW

FIRMWARE REV/VER

Displays Firmware Revision and Version of OPTIMizer or connected trip unit

 

 

 

CP

COPY COMMAND

Loads trip unit settings into OPTIMizer

 

 

 

DL

DOWNLOAD COMMAND

Sends stored settings in OPTIMizer to trip unit (valid password)

 

 

 

RE

RESET TRIP UNIT

Resets trip unit LEDs, historical current etc.

 

 

 

 

 

 

 

 

 

 

Effective 8/99