I.B. 29C892B |
|
| Page 9 | |
Table 2.1 Programmable Categories |
|
| ||
|
|
|
|
|
Displayed |
| Display |
| Additional Comments |
Menu Items |
| Definition |
| |
|
|
| ||
|
|
| ||
SA | SELECT ADDRESS | Network use only – permits selection of specific trip unit address within network | ||
|
|
| ||
FI | FIND BAUD/ADDR | Search to identify address and baud rate of connected trip unit (8 conductor custom phone cord only) | ||
|
|
| ||
ID | FIND PRODUCT ID | Identification of type and frame rating of connected breaker | ||
|
|
| ||
BA | CHANGE BAUD/ADDRESS | Permits the initial setup or changing of address and baud rate of connected trip unit – | ||
|
|
| valid password required to setup or change address | |
|
|
| ||
RP | RATING PLUG | Rating plug size installed in connected trip unit | ||
|
|
| ||
ME | METERED VALUES | Depending on trip unit connected, some or all of the values are displayed: | ||
| • | Current (A) | - Phases A, B, C, Ground and Neutral | |
| • | Energy (kWh) | - Total, Forward and Reverse | |
| • | Power (kW) | - Power and Peak Demand | |
| • | Power Factor |
|
|
| • | THD Currents (%) | - Phases A, B, C and Neutral | |
| • | Harmonic Content | - Phases A, B, C and Neutral | |
|
|
| ||
TM | TEST MODE | Provides for Phase or Ground, Trip or | ||
|
|
| ||
SP | SETPOINTS | Permits viewing, initial setup and changing of setpoints for connected trip unit – valid password | ||
|
|
| required to setup or change setpoints: | |
| • | LD | - | Long Delay Setting |
| • | LDTI | - | Long Delay Time |
| • | LDA | - | Long Delay Action |
| • | LDS | - | Long Delay Slope |
| • | SDPU | - | Short Delay Setting |
| • | SDTI | - | Short Delay Time |
| • | SDA | - | Short Delay Action |
| • | SDS | - | Short Delay Slope |
| • | IN | - | Instantaneous Setting |
| • | INA | - | Instantaneous Action |
| • | DSC | - | Discriminator |
| • | GFP | - | Ground Fault Setting |
| • | GFT | - | Ground Fault Time |
| • | GFA | - | Ground Fault Action |
| • | GFS | - | Ground Fault Slope |
| • | HLA | - | High Load Setting |
| • | PTM | - | Powered Thermal Memory |
| • | UPM | - | Unpowered Thermal Memory |
| • | FRQ | - | Line Frequency |
| • | NR | - | Neutral Ratio |
| • | AWC | - | Auto Waveform Capture |
| • | PI | - | Phase A Identification |
|
|
| ||
PA | PASSWORD | Permits authorized personnel to change or enter 4 digit password | ||
|
|
| ||
TC | TRIP EVENT COUNT | Display of number of circuit breaker automatic trip operations | ||
|
|
| ||
CT | Displays one of four possible modes of trip on most recent automatic trip operation: | |||
|
|
| • | Long Delay |
|
|
| • | Short Delay |
|
|
| • | Instantaneous |
|
|
| • | Ground Fault |
|
|
| ||
FW | FIRMWARE REV/VER | Displays Firmware Revision and Version of OPTIMizer or connected trip unit | ||
|
|
| ||
CP | COPY COMMAND | Loads trip unit settings into OPTIMizer | ||
|
|
| ||
DL | DOWNLOAD COMMAND | Sends stored settings in OPTIMizer to trip unit (valid password) | ||
|
|
| ||
RE | RESET TRIP UNIT | Resets trip unit LEDs, historical current etc. | ||
|
|
|
|
|
|
|
|
|
|
Effective 8/99