Page 18

I.B. 29C892B

<RP ME TM SP>

SETPOINTS

Figure 3-17 Cursor on Setpoints in Main Menu

LDA LDS

LD SLOPE

Figure 3-19 Setpoints Menu with Long Delay Slope Active

 

LD

LDTI

 

 

 

 

LD SET

 

Figure 3-18 Initial Setpoints Menu

Step 1: Use the On/Off pushbutton to turn the programmer on. The baud rate/address of the connected circuit breaker will automatically be identified and momentarily displayed (Figure 3 - 4), before the main menu is displayed (Figure 2 - 9).

Step 2: Use the R i g h t - A r r o w or Left-Arrow p u s h b u t- tons to move the cursor to Change Baud/Addr ( B A ) in the main menu (Figure 3 - 1 3) .

Step 3: Use the Select pushbutton to enter C h a n g e Baud/Addr (BA) and the present baud rate and address of the connected circuit breaker are displayed (Figure 3 - 1 4) .

Step 4: The blinking cursor indicates which digit of the display is active and able to be altered. Use the Up or Down p u s h b u t t o n s to change the active number. Use the Right-Arrowor Left- Arrow p u s h b u t t o n s to move the cursor from one digit to another.

Step 5: Once the desired baud rate and address are correctly displayed, hold Save p u s h b u t t o n depressed and depress Select p u s h b u t t o n. This simultaneous use of the two pushbuttons will enter the new baud rate and address. If the changes are accepted, the display will indicate the acceptance momentarily before returning to the main menu (Figure 3-15).

Notice: Keep in mind that a change in the baud rate and/or address is password protected. Step 5 may require the entry of a valid password before any changes are accepted. If the programmer was already turned on, and a valid

LDA

 

LDS

 

LD SLOPE

 

 

I2T

Figure 3-20 Long Delay Slope Present Setting Displayed

LDA

LDS

 

LD SLOPE

 

 

I4T

Figure 3-21 Long Delay Slope with New Setting Displayed

password was initially entered as described in paragraph 3-4 Method 1, entry of a password will not be required again and the baud rate and/or address changes will be saved. If a valid password was not initially entered, the display will require the entry of a valid password before any changes can be saved (Figure 3-8). Follow the steps outlined in paragraph 3- 4 Method 2 to enter a valid password.

Notice: Any time a circuit breaker address or baud rate is changed, verify that the correct address and baud rate are displayed by using the Right- Arrow or Left Arrow p u s h b u t t o n s to move the blinking cursor in the main menu to Find Baud/Addr (FI). Use the Select pushbutton to enter Find Baud/Addr (FI), and the newly assigned address and selected baud rate will be displayed.

3-6.2 INCOM CONNECTED ADDRESS AND BAUD RATE

Step 1: If the programmer is INCOM connected and a Baud Rate and/or Address Change to a net-

Effective 8/99